Rockwell Automation Publication 1407-UM001H-EN-P - November 2014
Detailed CGCM Unit Tag Descriptions
!PPENDIX
%
2EVERSE0OWER0ROTECTION/UTPUTSFROMTHE#'#-5NIT
•
RevPwrFlt
- This tag is used to communicate the occurrence of a Reverse
Power Fault to the host Logix controller. When this tag is a 1, it indicates
that a fault has occurred. The tag is latched until the host Logix controller
resets it by setting the FltReset tag.
2OTATING$IODE-ONITOR)NPUTSTOTHE#'#-5NIT
•
RotDiodeFltOutEn
- When this tag is a 1 in the configuration, and a
Shorted or Open Rotating Diode Fault occurs, the Fault Relay is
energized. When this tag is a 0 in the configuration, a these conditions has
no effect on the Fault Relay.
•
OpenDiodeMonitorLevel
- This tag sets the percent ripple at which the
rotating diode monitor alarm announces when an open diode condition
occurs.
•
ShortedDiodeMonitorLevel
- This tag sets the percent ripple at which
the rotating diode monitor alarm announces when a shorted diode
condition occurs.
•
DiodeMonitorTimeDly
- This tag sets the amount of time the CGCM
unit takes before the CGCM unit announces the rotating diodes have an
anomaly.
•
MainPole
- This tag sets the number of poles of the main field of the
generator.
•
ExciterPole
- This tag sets the number of poles of the exciter field of the
generator.
2OTATING$IODE-ONITOR/UTPUTSFROMTHE#'#-5NIT
•
RotDiodeFlt
- This tag is used to communicate the occurrence of a
Shorted or Open Rotating Diode Fault to the host Logix controller. When
this tag is a 1, it indicates that a fault has occurred. The tag is latched until
the host Logix controller resets it by setting the FltReset tag.
•
ShortedRotDiodeFlt
– This tag indicates that a Shorted Rotating Diode
Fault caused the RotDiodeFlt tag to be set.
•
OpenRotDiodeFlt
- This tag indicates that an Open Rotating Diode
Fault caused the RotDiodeFlt tag to be set.
0HASE2OTATION#HECK)NPUTSTOTHE#'#-5NIT
•
PhRotFltOutEn
- When this tag is a 1 in the configuration, and a Phase
Rotation Fault occurs the Fault Relay is energized. When this tag is a 0 in
the configuration, a Phase Rotation Fault has no effect on the Fault Relay.
Содержание 1407-CGCM
Страница 1: ...Combination Generator Control Module Catalog Numbers 1407 CGCM User Manual...
Страница 4: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 3UMMARY OF HANGES OTES...
Страница 8: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 0REFACE OTES...
Страница 12: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 HAPTER General Information OTES...
Страница 14: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 HAPTER Installation IGURE 5NIT VERALL IMENSIONS...
Страница 70: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 HAPTER CGCM Unit Operation OTES...
Страница 106: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 HAPTER CGCM Unit Configuration OTES...
Страница 126: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 HAPTER CGCM Unit Startup OTES...
Страница 152: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 HAPTER CGCM Unit Software Interface OTES...
Страница 168: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 HAPTER Troubleshooting OTES...
Страница 196: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 PPENDIX CGCM Unit Math Models OTES...
Страница 212: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 PPENDIX Specifications OTES...
Страница 250: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 NDEX OTES...
Страница 251: ......