Time Over-current Characteristic Curves
The CGCM unit has a maximum time dial setting of 9.9. The CGCM unit’s
equivalent time dial setting for the electromechanical maximum setting is
provided in the cross reference table even if it exceeds 9.9. This allows
interpolation as noted above.
CGCM unit time-current characteristics are determined by a linear
mathematical equation. The induction disk of an electromechanical relay has a
certain degree of non linearity due to inertial and friction effects. For this reason,
even though every effort has been made to provide characteristic curves with
minimum deviation from the published electromechanical curves, slight
deviations can exist between them.
In applications where the time coordination between curves is extremely close, we
recommend that you choose the optimal time dial setting by inspection of the
coordination study.
6OLTAGE2ESTRAINT
In Voltage Restraint mode, when the generator voltage is between 100% and 25%
of nominal voltage, the CGCM unit automatically reduces the selected
over-current setpoint linearly according to this formula:
Adjusted over-current setpoint = original over-current setpoint * generator
voltage / voltage restraint setpoint
The range of the voltage restraint setpoint is 0…200%. A setting of zero disables
the voltage restraint.
4ABLE#HARACTERISTIC#URVE#ROSSREFERENCE
#URVE
%QUIVALENT4O
0AGE
%LECTROMECHANICAL2ELAY4IME$IAL3ETTING
&ACTORY%QUIVALENT4IME$IAL3ETTING
1
ABB CO-2
173
0.3
0.8
1.7
2.4
3.4
4.2
5.0
5.8
6.7
7.7
8.6
9.7
3
ABB CO-5
175
0.4
0.8
1.5
2.3
3.3
4.2
5.0
6.0
7.0
7.8
8.8
9.9
5
ABB CO-6
177
0.5
1.1
2.0
2.9
3.7
4.5
5.0
5.9
7.2
8.0
8.9
10.1
6
ABB CO-7
178
0.4
0.8
1.7
2.5
3.3
4.3
5.3
6.1
7.0
8.0
9.0
9.8
7
ABB CO-8
179
0.3
0.7
1.5
2.3
3.2
4.0
5.0
5.8
6.8
7.6
8.7
10.0
9
ABB CO-9
181
0.3
0.7
1.4
2.1
3.0
3.9
4.8
5.7
6.7
7.8
8.7
9.6
11
ABB CO-11
183
0.3
0.7
1.5
2.4
3.2
4.2
5.0
5.7
6.6
7.8
8.5
10.3
8
GE IAC-51
180
0.6
1.0
1.9
2.7
3.7
4.8
5.7
6.8
8.0
9.3
10.6
10
GE IAC-53
182
0.4
0.8
1.6
2.4
3.4
4.3
5.1
6.3
7.2
8.4
9.6
2
GE IAC-55
174
0.2
1.0
2.0
3.1
4.0
4.9
6.1
7.2
8.1
8.9
9.8
4
GE IAC-66
176
0.4
0.9
1.8
2.7
3.9
4.9
6.3
7.2
8.5
9.7
10.9
12
GE IAC-77
184
0.5
1.0
1.9
2.7
3.5
4.3
5.2
6.2
7.4
8.2
9.9
Содержание 1407-CGCM
Страница 1: ...Combination Generator Control Module Catalog Numbers 1407 CGCM User Manual...
Страница 4: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 3UMMARY OF HANGES OTES...
Страница 8: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 0REFACE OTES...
Страница 12: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 HAPTER General Information OTES...
Страница 14: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 HAPTER Installation IGURE 5NIT VERALL IMENSIONS...
Страница 70: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 HAPTER CGCM Unit Operation OTES...
Страница 106: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 HAPTER CGCM Unit Configuration OTES...
Страница 126: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 HAPTER CGCM Unit Startup OTES...
Страница 152: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 HAPTER CGCM Unit Software Interface OTES...
Страница 168: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 HAPTER Troubleshooting OTES...
Страница 196: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 PPENDIX CGCM Unit Math Models OTES...
Страница 212: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 PPENDIX Specifications OTES...
Страница 250: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 NDEX OTES...
Страница 251: ......