Detailed CGCM Unit Tag Descriptions
!PPENDIX
%
,OSSOF/PERATING0OWER)NPUTSTOTHE#'#-5NIT
•
LossPMGFltOutEn
- When this tag is a 1 in the configuration, and a Loss
of PMG Fault occurs the Fault Relay is energized. When this tag is a 0 in
the configuration, a Loss of PMG Condition has no effect on the Fault
Relay.
,OSSOF/PERATING0OWER/UTPUTSFROMTHE#'#-5NIT
•
LossPMGFlt
- This tag is used to communicate the occurrence of a Loss of
PMG Fault to the host Logix controller. When this tag is a 1, it indicates
that a fault has occurred. The tag is latched until the host Logix controller
resets it by setting the FltReset tag.
2EVERSE6!2)NPUTSTOTHE#'#-5NIT
•
RevVARFltOutEn
- When this tag is a 1 in the configuration, and a
Reverse VAR Fault occurs (as defined by the Rev_kVAR Setpt tag), the
Fault Relay is energized. When this tag is a 0 in the configuration, an
Over-voltage Condition has no effect on the Fault Relay.
•
Rev_kVAR_Setpt
- This tag configures the generator reverse kVAR
setpoint at which the CGCM unit recognizes a reverse kVAR (loss of
excitation) condition is present and starts timing to trip based on the
Reverse kVAR fault Delay setting.
•
Rev_kVAR_TimeDly
- This tag configures the time to
shutdown/annunciate once the generator reverse kVAR setpoint has been
exceeded.
2EVERSE6!2/UTPUTSFROMTHE#'#-5NIT
•
RevVARFlt
- This tag is used to communicate the occurrence of a Reverse
VAR Fault to the host Logix controller. When this tag is a 1, it indicates
that a fault has occurred. The tag is latched until the host Logix controller
resets it by setting the FltReset tag.
$EFINITE4IME/VERFREQUENCY)NPUTSTOTHE#'#-5NIT
•
OvrFreqFltOutEn
- When this tag is a 1 in the configuration, and an
Over-frequency Fault occurs (as defined by the OvrFreqSetpt tag), the
Fault Relay is energized. When this tag is a 0 in the configuration, an
Over-frequency Condition has no effect on the Fault Relay.
•
OvrFreqSetpt
- This tag configures the generator over-frequency setpoint
at which the CGCM unit recognizes an over-frequency condition is
present and starts timing to trip based on the Over-frequency Time Delay.
•
OvrFreqTimeDly
- This tag configures the time to shutdown/annunciate
once the generator Over-frequency Setpoint has been exceeded.
Содержание 1407-CGCM
Страница 1: ...Combination Generator Control Module Catalog Numbers 1407 CGCM User Manual...
Страница 4: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 3UMMARY OF HANGES OTES...
Страница 8: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 0REFACE OTES...
Страница 12: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 HAPTER General Information OTES...
Страница 14: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 HAPTER Installation IGURE 5NIT VERALL IMENSIONS...
Страница 70: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 HAPTER CGCM Unit Operation OTES...
Страница 106: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 HAPTER CGCM Unit Configuration OTES...
Страница 126: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 HAPTER CGCM Unit Startup OTES...
Страница 152: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 HAPTER CGCM Unit Software Interface OTES...
Страница 168: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 HAPTER Troubleshooting OTES...
Страница 196: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 PPENDIX CGCM Unit Math Models OTES...
Страница 212: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 PPENDIX Specifications OTES...
Страница 250: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 NDEX OTES...
Страница 251: ......