
Rockwell Automation Publication 1407-UM001H-EN-P - November 2014
Detailed CGCM Unit Tag Descriptions
!PPENDIX
%
,INEDROP#OMPENSATION)NPUTSTOTHE#'#-5NIT
•
LineDropComp
- This tag configures the amount of voltage droop that is
experienced during paralleling generator applications.
5NDEREXCITATION,IMIT)NPUTSTOTHE#'#-5NIT
•
UEL_En
- Setting this tag enables the Under-excitation Limiting
function.
•
UEL_Kg
- This tag lets you adjust the proportional gain of the
Under-excitation limiter. It also determines the response of the limiter to
an Under-excitation event. Increasing this term increases the speed of the
response of the limiter.
•
UEL_Ki
- This tag lets you adjust coarse loop gain and overall gain of the
Under-excitation limiter. This tag determines the characteristic of the
dynamic response to an Under-excitation event.
•
UEL_Curve_W_Pt1
– This tag is used as the Watt coordinate in the first
Watt, VAR coordinate pair, that, in combination with four other Watt,
VAR coordinate pairs, lets you enter an Under-excitation Limiting curve.
•
UEL_Curve_W_Pt2
– This tag is used as the Watt coordinate in the
second Watt, VAR coordinate pair, that, in combination with four other
Watt, VAR coordinate pairs, lets you enter an Under-excitation Limiting
curve.
•
UEL_Curve_W_Pt3
- This tag is used as the Watt coordinate in the third
Watt, VAR coordinate pair, that, in combination with four other Watt,
VAR coordinate pairs, lets you enter an Under-excitation Limiting curve.
•
UEL_Curve_W_Pt4
- This tag is used as the Watt coordinate in the
fourth Watt, VAR coordinate pair, that, in combination with four other
Watt, VAR coordinate pairs, lets you enter an Under-excitation Limiting
curve.
•
UEL_Curve_W_Pt5
- This tag is used as the Watt coordinate in the fifth
Watt, VAR coordinate pair, that, in combination with four other Watt,
VAR coordinate pairs, lets you enter an Under-excitation Limiting curve.
•
UEL_Curve_VAR_Pt1
- This tag is used as the VAR coordinate in the
first Watt, VAR coordinate pair, that, in combination with four other
Watt, VAR coordinate pairs, lets you enter an Under-excitation Limiting
curve.
•
UEL_Curve_VAR_Pt2
- This tag is used as the VAR coordinate in the
second Watt, VAR coordinate pair, that, in combination with four other
Watt, VAR coordinate pairs, lets you enter an Under-excitation Limiting
curve.
•
UEL_Curve_VAR_Pt3
- This tag is used as the VAR coordinate in the
third Watt, VAR coordinate pair, that, in combination with four other
Watt, VAR coordinate pairs, lets you enter an Under-excitation Limiting
curve.
Содержание 1407-CGCM
Страница 1: ...Combination Generator Control Module Catalog Numbers 1407 CGCM User Manual...
Страница 4: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 3UMMARY OF HANGES OTES...
Страница 8: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 0REFACE OTES...
Страница 12: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 HAPTER General Information OTES...
Страница 14: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 HAPTER Installation IGURE 5NIT VERALL IMENSIONS...
Страница 70: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 HAPTER CGCM Unit Operation OTES...
Страница 106: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 HAPTER CGCM Unit Configuration OTES...
Страница 126: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 HAPTER CGCM Unit Startup OTES...
Страница 152: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 HAPTER CGCM Unit Software Interface OTES...
Страница 168: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 HAPTER Troubleshooting OTES...
Страница 196: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 PPENDIX CGCM Unit Math Models OTES...
Страница 212: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 PPENDIX Specifications OTES...
Страница 250: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 NDEX OTES...
Страница 251: ......