Detailed CGCM Unit Tag Descriptions
/VEREXCITATION,IMIT)NPUTSTOTHE#'#-5NIT
•
OEL_En
– Setting this tag enables the Over-excitation Limiting function.
•
OEL_Kg
- This tag lets you adjust the proportional gain of the
Over-excitation limiter. It also determines the response of the limiter to an
Over-excitation event.
•
OEL_Ki
- This tag lets you adjust coarse loop gain and overall gain of the
Over-excitation limiter. This tag determines the characteristic of the
dynamic response to an Over-excitation event.
•
OEL_OnLineHiSetpt
– This tag sets the high current level for the online
over-excitation limiting function. The CGCM unit’s over-excitation
limiter limits excitation current at this level. Operation at this level is
allowed for a time no longer than programmed in the
OEL_OnLineHiTimeDly tag.
•
OEL_OnLineHiTimeDly
– This tag sets the amount of time the online
over-excitation limiting function lets the unit operate at the excitation
current level programmed in the OEL_OnLineHiSetpt tag.
•
OEL_OnLineMedSetpt
-
This tag sets the medium current level for the
online over-excitation limiting function. Operation at this level is allowed
for a time no longer than programmed in the OEL_OnLineMedTimeDly
tag.
•
OEL_OnLineMedTimeDly
– This tag sets the amount of time the online
over-excitation limiting function lets the unit operate at the excitation
current level programmed in the OEL_OnLineMedSetpt tag.
•
OEL_OnLineLoSetpt
-
This tag sets the low current level for the online
over-excitation limiting function. Operation at this level is allowed
continuously.
•
OEL_Off LineHiSetpt
– This tag sets the high current level for the
offline over-excitation limiting function. The CGCM unit’s
over-excitation limiter limits excitation current at this level. Operation at
this level is allowed for a time no longer than programmed in the
OEL_OffLineHiTimeDly tag.
•
OEL_Off LineHiTimeDly
- This tag sets the amount of time the offline
over-excitation limiting function lets the unit operate at the excitation
current level programmed in the OEL_OffLineHiSetpt tag.
•
OEL_Off LineLoSetpt
- This tag sets the low current level for the offline
over-excitation limiting function. Operation at this level is allowed
continuously.
/VEREXCITATION,IMIT/UTPUTSFROMTHE#'#-5NIT
•
OEL_Active
– This tag is set to 1 when the exciter is operating in the
Over-excitation Limiting mode.
Содержание 1407-CGCM
Страница 1: ...Combination Generator Control Module Catalog Numbers 1407 CGCM User Manual...
Страница 4: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 3UMMARY OF HANGES OTES...
Страница 8: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 0REFACE OTES...
Страница 12: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 HAPTER General Information OTES...
Страница 14: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 HAPTER Installation IGURE 5NIT VERALL IMENSIONS...
Страница 70: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 HAPTER CGCM Unit Operation OTES...
Страница 106: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 HAPTER CGCM Unit Configuration OTES...
Страница 126: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 HAPTER CGCM Unit Startup OTES...
Страница 152: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 HAPTER CGCM Unit Software Interface OTES...
Страница 168: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 HAPTER Troubleshooting OTES...
Страница 196: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 PPENDIX CGCM Unit Math Models OTES...
Страница 212: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 PPENDIX Specifications OTES...
Страница 250: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 NDEX OTES...
Страница 251: ......