Rockwell Automation Publication 1407-UM001H-EN-P - November 2014
#HAPTER
Troubleshooting
4ABLE,IMITING-ODES/%,
3YMPTOM
-OST,IKELY#AUSE
$IAGNOSTIC!CTION
#ORRECTIVE!CTION
Excitation Current exceeds the
programmed OEL limit (OEL does not
limit/activate)
OEL not enabled
Check tag
/%,?%N
and configuration
Correct logic or configuration
as required
OEL Gain misadjusted
Force into OEL
Adjust gains as required
OEL not configured
Check OEL settings against generator
excitation requirements / limits
Correct as required
Metering error
See Metering troubleshooting
See Metering troubleshooting
Excitation is unstable when OEL is
active
OEL Gain misadjusted
Force into OEL
Adjust gains as required
4ABLE2EAL0OWER,OAD3HARING
3YMPTOM
-OST,IKELY#AUSE
$IAGNOSTIC!CTION
#ORRECTIVE!CTION
Units do not share load
Load share lines not properly
connected
Measure voltage at each LS+/-
terminal. Verify voltage
represents PU load
Re-connect LS lines
Open LS terminals; apply a load,
measure LS voltage.
Voltage equals (kW/Rated
kW)*LSFSVoltage
If Voltage not correct, replace CGCM
unit after verifying configuration
settings
Load sharing not enabled
Check output tag kW_LS_EN is
set and input tag
kW_LS_ACTIVE is true
If Loadsharing must be disabled no
anomaly is present, otherwise correct
loadsharing logic for tag kW_LS_En
CGCM unit not properly configured
Check configuration parameters
are properly set. Refer to Load
Share tab, Chapter 4
Input correct configuration
parameters
Wiring errors cause CGCM unit to not
meter kW properly
Check kW indication from CGCM
unit against second meter for
accurate kW indication
Correct wiring errors
Governor not responding to load
share error
Observe that load share error is
being received from CGCM unit
in host controller
Correct anomaly in Host controller if a
valid load share error is received
Units do not share load equally: one
unit increases the other unit
decreases
Load share lines connected with
polarity reversed
Observe that load share error is
being received from CGCM unit
in host controller and error
polarity is correct
Correct polarity on LS lines
Содержание 1407-CGCM
Страница 1: ...Combination Generator Control Module Catalog Numbers 1407 CGCM User Manual...
Страница 4: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 3UMMARY OF HANGES OTES...
Страница 8: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 0REFACE OTES...
Страница 12: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 HAPTER General Information OTES...
Страница 14: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 HAPTER Installation IGURE 5NIT VERALL IMENSIONS...
Страница 70: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 HAPTER CGCM Unit Operation OTES...
Страница 106: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 HAPTER CGCM Unit Configuration OTES...
Страница 126: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 HAPTER CGCM Unit Startup OTES...
Страница 152: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 HAPTER CGCM Unit Software Interface OTES...
Страница 168: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 HAPTER Troubleshooting OTES...
Страница 196: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 PPENDIX CGCM Unit Math Models OTES...
Страница 212: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 PPENDIX Specifications OTES...
Страница 250: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 NDEX OTES...
Страница 251: ......