Detailed CGCM Unit Tag Descriptions
!PPENDIX
%
%XCITATION#ONTROL&EATURES
This section describes the excitation control features.
3OFT3TART)NPUTSTOTHE#'#-5NIT
•
SoftStart_InitLevel
- This tag configures the generator voltage that is
generated immediately after enabling the CGCM unit. This parameter is
based on a percentage of the nominal generator voltage.
•
SoftStartTime
- This tag configures the time it takes to go from the Soft
Start Initial Voltage to the nominal generator voltage.
$ROOP2EACTIVE#URRENT#OMPENSATION )NPUTSTOTHE#'#-5NIT
•
Droop_CCC_Select
– If Droop is enabled, this tag selects CCC when set
to 1 or Droop when set to 0.
•
V_DroopEn
– This tag configures whether Droop is enabled
•
V_DroopSetpt
- This tag configures the amount of voltage droop that is
experienced during paralleling generator applications.
5NDERFREQUENCY,IMIT)NPUTSTOTHE#'#-5NIT
•
VperHz_HiKneeFreq
- The Knee Frequency tag configures the frequency
at which the V/Hz characteristic starts to reduce the generator voltage as a
function of generator frequency.
•
VperHz_HiSlope
- The Upper Slope tag configures the rate at which the
V/Hz characteristic reduces the generator voltage as a function of
generator frequency. The steeper the slope the faster the prime mover is
unloaded and smaller the frequency variations are experienced during load
applications.
•
VperHz_LoKneeFreq
- The Knee Frequency tag configures the frequency
at which the V/Hz characteristic starts to reduce the generator voltage as a
function of generator frequency.
•
VperHz_LoSlope
- The Lower Slope tag configures the rate at which the
V/Hz characteristic reduces the generator voltage as a function of
generator frequency after the Lower Knee Frequency is exceeded.
#ROSSCURRENT#OMPENSATION)NPUTSTOTHE#'#-5NIT
•
Droop_CCC_Select
– If Droop is enabled, this bit selects CCC when set
to 1 or Droop when set to 0.
•
CrossCurrentGain
- This setting lets you adjust the gain of the cross
current input. The actual value measured by the cross current input is
multiplied by this setting. It can be used to improve the var sharing
between machines connected in cross current.
Содержание 1407-CGCM
Страница 1: ...Combination Generator Control Module Catalog Numbers 1407 CGCM User Manual...
Страница 4: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 3UMMARY OF HANGES OTES...
Страница 8: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 0REFACE OTES...
Страница 12: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 HAPTER General Information OTES...
Страница 14: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 HAPTER Installation IGURE 5NIT VERALL IMENSIONS...
Страница 70: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 HAPTER CGCM Unit Operation OTES...
Страница 106: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 HAPTER CGCM Unit Configuration OTES...
Страница 126: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 HAPTER CGCM Unit Startup OTES...
Страница 152: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 HAPTER CGCM Unit Software Interface OTES...
Страница 168: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 HAPTER Troubleshooting OTES...
Страница 196: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 PPENDIX CGCM Unit Math Models OTES...
Страница 212: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 PPENDIX Specifications OTES...
Страница 250: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 NDEX OTES...
Страница 251: ......