7 Operations
7.9
Operating a Water Heating or Cooling Contherm™ or Brine Cooling Contherm™
The installation and set-up of the Contherm
™
for a water or brine cooled configuration is described in Chapter Five, Section
5.10 Installing A Water or Brine Cooling System. Typical installation drawings of the configuration are provided in Figure 5-13.
Refer to those portions of Chapter Five as necessary while performing the initial start-up and operating procedure that
is provided in Table 7-11.
Two typical Contherm
™
cooling system configurations are shown in Figure 5-13. One configuration shows an open loop set-up
where product temperature control is required. In this configuration, the cooling water/brine is piped in a series arrangement
through each Contherm
™
. This arrangement minimizes water consumption while maintaining high velocities through the media
annulus thereby ensuring efficient heat transfer.
The second configuration shows a temperature control loop using a centrifugal pump. In this configuration, the pump circulates
the cooling fluid through the Contherms
™
media jacket. In configurations with more than one Contherm
™
, this set-up is usually
utilized for the final Contherm
™
when the product outlet temperature must be controlled.
Table 7-11. Start-Up and Operation of Water or Brine Cooled Contherm
™
Step
Action
1
Using water as the test “product,” start flowing it through the Contherm
™
via the product inlet. When water begins
exiting the unit’s product chamber via the product outlet, start the rotor.
Note: For best results, adjust the flow rate and temperature profile of the water
2
Turn on the water or brine cooling system. Inspect the media piping for leaks. If your system does not contain a
temperature control loop, adjust the coolant flow to control the product outlet temperature and proceed to Step 5.
3
Set the automatic temperature controller to 50° F (10° C). After several minutes of operation, check product inlet
and outlet temperatures. The outlet temperature gauge should read approximately 50° F (10° C). Repeat this
step for several other temperature settings.
4
Set the controller to your desired product temperature setting. The product outlet temperature gauge should reach
this temperature within five to ten minutes.
5
When you are satisfied that the Contherm
™
is operating properly with water as the product, drain and flush the
water “product” from the system.
6
Your Contherm
™
is now ready to begin service.
Note: The product should be flowing through the system and diverted back to the source before the cooling media
is turned on. This will prevent a freeze up from occurring as the product will not be exposed to a colder than
normal cylinder surface. Divert the product back to the source until the product is at the desired temperature, then
begin the forward (process) flow.
57
Содержание Contherm 6X11
Страница 2: ......
Страница 10: ...2 Safety Summary Figure 2 1B Safety Warnings Refer to section 2 3 for safety and inspection symbols 10...
Страница 52: ...7 Operations Figure 7 2A Installing the Rotor Helper Plate Figure 7 2A Installing the Rotor Helper Plate 52...
Страница 66: ...8 Inspection Maintenance Figure 8 2 Component List Figure 8 2 66...
Страница 88: ...8 Inspection Maintenance Figure 8 13 Upper Bearings Direct Coupled Electric Drive Motor 88...
Страница 99: ...8 Inspection Maintenance Figure 8 18B CONTHERM Hydraulic Lift Assembly With Hold Down 99...
Страница 117: ...10 Appendix A Additional Installation Drawings 117...
Страница 118: ...10 Appendix A Additional Installation Drawings 10 Install the hydraulic lift pump and stack valve components 118...
Страница 123: ...123...