FOR VAPOR PIPING ONLY, a 8” or more
rise could be added if needed. (See below)
Main Unit and Piping
Electrical
Test Operation
Reference
17
4. Refrigerant Piping
�
Secure straight portion for 26” (660 mm) or more after branching of the Combination Multi connection kit.
�
FOR VAPOR PIPING ONLY, if the connection piping length is 6-1/2’ or more, add a 8” or more rise within
6-1/2’ from the Combination Multi connection kit.
6-1/2’ (2 m) or less
6-1/2’ (2 m) or less
6-1/2’ (2 m) or more
6-1/2’ (2 m)
or less
8 inch (200 mm)
6-1/2’ (2 m) or less
6-1/2’ (2 m) or more
26” (660 mm)
or more