Suburban DynaLine Owner's Manual 04/2021 Rev.4
20
Dynaline 3 Model Identification
Example
D
Y
N
A
0
7
A
C
A
0
1
2
L
F
2
0
1
0
0
Position
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
1
Unit Designation
Dynaline 3™
2
3
4
5
Nominal Cooling Capacity
07
= 7,600
09
= 9,500
12
= 11,500
16
= 15,000
6
7
System Type
AC
= Air Conditioner
8
9
Power Supply (Volts-Phase-Hz)
A
= 208/230-1-60
V
= 277-1-60
10
Nominal Heat Input
012
= 12,000
020
= 18,000
022
= 20,000
11
12
13
Fuel Type
N
= Natural Gas
L
= LP Gas
14
Gas Connection
F
= Front
15
Revision Code
20
16
17
Cabinet Color
100
= Champaign Beige
800
= Mesa Tan
416
= White
200
= Gray
18
19
Requirements for Installation Commonwealth of Massachusetts
For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in part for
residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is
less than seven (7) feet above finished grade in the area of the venting, including but not limited to decks and porches, the following
requirements shall be satisfied:
1. INSTALLATION OF CARBON MONOXIDE DETECTORS.
At the time of installation of the side wall horizontal vented
gas fueled equipment, the installing plumber or gas fitter shall observe that a hard wired carbon monoxide detector with
an alarm and battery back-up is installed on the floor level where the gas equipment is to be installed. In addition, the
installing plumber or gas fitter shall observe that a battery operated or hard wired carbon monoxide detector with an alarm
is installed on each additional level of the dwelling , building or structure served by the side wall horizontal vented gas fueled
equipment. It shall be the responsibility of the property owner to secure the services of qualified licensed professionals for
the installation of hard wired carbon monoxide detectors.
a.
In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or an attic, the
hard wired carbon monoxide detector with alarm and battery back-up may be installed on the next adjacent floor
level.
b.
In the event that the requirements of this subdivision can not be met at the time of completion of installation, the
owner shall have a period of thirty (30) days to comply with the above requirements; provided, however, that during
said thirty (30) day period, a battery operated carbon monoxide detector with an alarm shall be installed.
2. APPROVED CARBON MONOXIDE DETECTORS.
Each carbon monoxide detector as required in accordance with the
above provisions shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS certified.
3. SIGNAGE.
A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum
height of eight (8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled
heating appliance or equipment. The sign shall read, in print size no less than one0half (½) inch in size,
“GAS VENT
DIRECTLY BELOW, KEEP CLEAR OF ALL OBSTRUCTIONS”
.
4. INSPECTION.
The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve
the installation unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in
accordance with the provisions of 248 CMR 5.08(2)(a) 1 through 4.
(b) EXEMPTIONS: The following equipment is exempt from 248 CMR 5.08(2)(a)1 through 4:
1.
The equipment listed in Chapter 10 entitled “Equipment Not Required To Be Vented” in the most current edition of NFPA 54
as adopted by the Board; and
2.
Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure separate from the
dwelling, building or structure used in whole or in part for residential purposes.