Suburban DynaLine Owner's Manual 04/2021 Rev.4 

10

3.

  If the main burner flame is sensed, the burner will remain on until the thermostat is satisfied. If the flame is not sensed, the gas 

valve closes and the ignition sequence automatically repeated two (2) times. If the burner does not light during this trial for ignition 

period, the unit will lock-out for one (1) hour and then re-set automatically.

NOTE

: If lock-out should occur, the unit can be re-set manually by breaking the power to the unit. When power is restored, the 

ignition procedures can be repeated. Should repeated lock-out occur, shut unit down and contact your gas service agency.

4.

  After proof of ignition (burner lights and flame properly sensed) a circuit is completed to the room air blower and the blower comes 

on.

5.

  When the thermostat is satisfied, the valve closes. The combustion air motor will remain on for a 20 second purge cycle, then goes 

off. The room air blower will continue to operate for approximately 90 seconds at which time the circuit is opened and the room air 

blower goes off.

NOTE

: If your unit is controlled by a wall thermostat, the ignition sequence is the same as with built-in thermostat; however, the 

temperature setting and system functions are selected at the wall thermostat. The “Fan” speed is controlled in the same manner 

as with built-in thermostat.

B.  COOLING MODE - Normal Operation (See Figure 13)

1.

  Depress “System” key pad until cool lamp is illuminated.

2.

   Depress “Fan” key pad until desired speed lamp is illuminated.

3.

  Set thermostat to desired setting by depressing temperature indicating arrows until desired temperature is displayed.

4. 

If the thermostat circuit is closed at the setting chosen in Step 3, the cooling cycle begins. NOTE: On initial start-up, the compressor 

will not be energized for five (5) minutes even though the system functions have been properly selected.

Whenever the outside temperature is below 65

°

 and the humidity is high, frost could form on the evaporator coil during extended cooling 

operation. To eliminate frost formation, a de-ice switch in the compressor circuit will sense a frost condition and open the compressor 

circuit. Upon temperature rise, the switch will close and the compressor will again come on provided the thermostat is still calling for 

cooling.

NOTE

: This unit has a built-in 5 minute delay between compressor cycles. Any time the compressor cycle is interrupted either manually, 

through thermostat, a power interruption, etc., the compressor will not restart for 5 minutes.

C.  CARBON MONOXIDE (CO) DETECTOR (See Figure 14)

This Dynaline unit is equipped with an integrated carbon monoxide (CO) detector (System Sensor Model C01224T). To access the CO 

detector remove the front panel. The CO detector is located on the left side of the unit and consists of the detector and a power supply 

board. See figure 14. The system connected carbon monoxide detector known as CO1224T was tested at a National Recognized Test 

Laboratory and has been verified to perform in the detection of carbon monoxide up to 12,000 ft above sea level.  During this testing by the 

National Recognized Test Laboratory the detector alarmed within the time specified by ANSI/UL 2034 for carbon monoxide concentrations 

of 70, 150 and 400 parts per million (ppm). 

4 PIN FEMALE HOUSING

4 PIN MALE HOUSING

(ONLY FOR UNITS WITH

OPTIONAL CARBON

MONOXIDE DETECTOR)

RESET

BUTTON

TEST/HUSH 

BUTTON

CO DETECTOR OPERATION MODES

  

OPERATION 

MODE

GREEN 

LED

RED LED

SOUNDER

Normal 

(Standby)

Blink 1 per 

minute

OFF

OFF

Alarm

OFF

Temp 4 

pattern

Temp 4

pattern

Alarm Test

OFF

Temp 4 

pattern

Temp 4

pattern

End of Life

OFF

OFF

OFF

CO Trouble

OFF

Blink 1 per 

minute

OFF

Power Loss / 

Cell Fault

OFF

OFF

OFF

CARBON MONOXIDE (CO) DETECTOR

Figure 15

Alarm Test:

Will send alarm signal to panel.

Hush feature / Alarm Silence:

The audible alarm can be silenced for 5 minutes by pushing the button marked “Test/Hush”.  The red alarm light will continue to flash in 

temp 4 pattern.  If carbon monoxide is still present after the 5 minute hush period, the audible alarm will sound.  The hush feature will not 

operate at levels above 350 ppm carbon monoxide.  

Содержание DYNA07AC

Страница 1: ...ot store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrical...

Страница 2: ...Your unit should be inspected immediately after unpacking to determine if any damage is present due to shipping or handling If any damage is discovered do not install the unit Notify the transportatio...

Страница 3: ...ot install in an alcove or recess Special sleeve and grille applications must be brought to the attention of Suburban Applied Products as they may impair the operation of the unit IMPORTANT Installati...

Страница 4: ...heavy under conditions of extreme humidity for extended periods of time The drain tube assemblies may be installed externally on rear flange of the wall sleeve or underneath the wall sleeve to the ext...

Страница 5: ...STALLATION FRONT GAS HOOKUP WALL INSTALLATION FRONT GAS HOOK UP Figure 5 GASKET NOTCH FOR OPTIONAL REAR GAS HOOKUP BE SURE DRAIN HOLES ARE TO OUTSIDE REAR FRONT SLEEVE TOP INSERT SIDES BETWEEN TOP FLA...

Страница 6: ...xisting DynaLine units with new DynaLine 3 units it is recommended to replace the wall sleeve as well During the replacement process the sleeve may become damaged or incorrectly aligned If sleeve inst...

Страница 7: ...al supply Refer to Figure 10 for centerline location of gas connection and electrical connection when unit is installed into wall sleeve NOTE This unit is factory set for 230 volt operation If you wis...

Страница 8: ...l Gas 5 W C 7 W C Liquefied Petroleum LP Gas 11 W C 13 W C Water Column OPERATING PRESSURE All units for burning natural gas are equipped with a valve having a built in regulator preset at 3 5 W C pre...

Страница 9: ...an speed 1 Open the manual shut off valve The valve is fully open when the handle is level or parallel to the gas line Never attempt to operate unit with manual valve partially closed 2 Depress System...

Страница 10: ...m on the evaporator coil during extended cooling operation To eliminate frost formation a de ice switch in the compressor circuit will sense a frost condition and open the compressor circuit Upon temp...

Страница 11: ...ve will close Do not ignore the alarm and shutdown Immediately move to a spot where fresh air is available preferably outdoors Find a phone in an area where the air is safe and call your building mana...

Страница 12: ...In rare instances the sounding of a warning device can cause temporary or permanent hearing loss Telephone lines needed to transmit alarm signals from a premises to a central station may be out of ser...

Страница 13: ...ect electrical supply before cleaning unit or performing any maintenance The unit should be inspected by a qualified service person yearly before turning the unit on heat for the winter Particular att...

Страница 14: ...BURNER OBSERVATION WINDOW YELLOW OUTER FLAME ERRATIC PATTERN ORANGE YELLOW INNER FLAME ERRATIC PATTERN Figure 17 Filter Removal 1 The filter is located behind the cabinet front Remove cabinet front by...

Страница 15: ...OTES The efficiency rating of this unit is a product thermal efficiency rating determined under continuous operating conditions and was determined independent of any installed system IMPORTANT Childre...

Страница 16: ...BK BL Y BK Y R R R R O BR BK BK COMPRESSOR RELAY Y Y L2 R BK L1 WHITE YELLOW BROWN BLACK RED BLUE ORANGE COLOR R W Y BR BL BK CODE O FLAME CONDENSER BK BL MODULE BOARD O BR 1 2 3 4 BUILT IN T STAT PRO...

Страница 17: ...EET 3m HORIZONTALLY C CLEARANCE TO WINDOW OR DOOR THAT MAY BE OPENED a a L CLEARANCE ABOVE PAVED SIDEWALK OR PAVED DRIVEWAY LOCATIED ON PUBLIC PROPERTY 7 FEET 2 13m a D VERTICAL CLEARANCE TO VENTILATE...

Страница 18: ...ILLE A ARCHITECTURAL STYLE GRILLES NATURAL FINISH ALUMINUM GRILLE STOCK NO 1420 DARK BRONZE FINISH GRILLE STOCK NO 1418 INTRODUCTION These architectural grilles are designed to be used as an optional...

Страница 19: ...adaptor is 43 1 4 On model DYNA12AC and DYNA16AC additional lengths may be added If additional length is required connector assembly No K 10734 may be used No more than two 2 connectors may be used Ma...

Страница 20: ...ified licensed professionals for the installation of hard wired carbon monoxide detectors a In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or an...

Страница 21: ...vice labor diagnosis calls filter driers refrigerant or any other material charges 2 Damages caused by shipping accident abuse negligence misuse fire flood or Acts of God 3 Damages caused by operating...

Страница 22: ...e in heat when the temperature drops below about 45 F when the unit is in STANDBY HEAT and COOL mode This mode can be disabled if desired If freeze protection is desired when operated from a wall moun...

Страница 23: ...IRE OR TYPE 150 C WIRE WHERE SPECIFIED OR ITS EQUIVALENT 105 C THERMOPLATIC 14 A W G WIRE TGS 200 C 18GA STRANDED TEFLON COATED ROCKER SWITCH R BL O N C FLUE LIMIT R HIGH LOW L1 COMB COND BLWR FLAME D...

Страница 24: ...WHITE BLACK 2 4 3 1 BL BL W W BK IGNITOR RELAY BK ROCKER SWITCH BK BL R R O O 24VAC GND CONT GAS VALVE POWER SUPPLY BOARD CO DETECTOR BL Y BK GY R BL T T NC C T C A NO BR BL BL Y Y BR O 4 3 2 1 BL O...

Страница 25: ...k for fault numbers associated with the HEAT mode Press the SYSTEM key again to go from HEAT to COOL Check for fault numbers associated with the COOL mode The SERVICE menu will Time Out automatically...

Страница 26: ...the lockout expires 15 Loss of pressure switch lockout Pressure switch contact open during heating operation After 5 trips of the pressure switch a 20 minute lockout begins code 15 is registered and t...

Страница 27: ...it de cet appareil ou de tout autre appareil QUEFAIRESIVOUSSENTEZUNEODEURDEGAZ Ne pas tenter d allumer d appareils Ne touchez aucun interrupteur Ne pas vous servir des t l phones se trouvant dans le b...

Страница 28: ...imm diatement apr s le d ballage pour d terminer la pr sence d ventuels dommages imputables au transport et aux manutentions S il y a des dommages ne pas installer l appareil Aviser imm diatement le...

Страница 29: ...install e conform ment aux indications de la figure 5 ou 6 lorsque l appareil est plac dans la gaine murale l air de ventilation est pr lev dans l atmosph re ext rieure Ne pas installer l appareil da...

Страница 30: ...ement en s curit de l appareil ou l installation correcte des canalisations d arriv e de gaz et du c ble d alimentation lectrique 8 Le panneau avant de la caisse est exp di avec le ch ssis Pour garant...

Страница 31: ...ALE SURFACE DE FINITION DU MUR EXT RIEUR 1 INSTALLATION MURALE RACCORDEMENT PAR L AVANT LA CANALISATION DE GAZ Figure 5 SOMMET JOINT ENCOCHE POUR CONNECTION OPTIONELLE EN ARRI RE DU GAZ VEILLER PLACER...

Страница 32: ...qu elle d passe d au moins 1 4 po au del de la surface finale du mur ext rieur voir figure 5 NOTE Pour une installation avec gaine murale et d passement dans la pi ce de 4 po ou plus on doit utiliser...

Страница 33: ...ommutateur de configuration no 1 du thermostat la position on Voir figure 11 Pour r initialiser les contr les teignez puis rallumez le REMARQUE Raccordement thermostat distance remplace le thermostat...

Страница 34: ...iatement en amont du point de raccordement de l appareil la canalisation de gaz Lors de tout test de pressurisation ex cut sur le syst me une pression sup rieure 1 2 lb po2 rel 3 5 kPa il faut que l a...

Страница 35: ...er 2 Appuyez simultan ment sur les boutons WARMER COOLER et FAN nF va s afficher quand la protection contre le gel est d sactiv e et FP va s afficher quand la protection contre le gel est activ e REMA...

Страница 36: ...mostat manifeste encore une demande de refroidissement NOTE Une p riode d attente de 5 minutes est incorpor e entre les p riodes de fonctionnement du compresseur Apr s chaque interruption du fonctionn...

Страница 37: ...r et appelez votre gestionnaire d immeuble et leur demander d avoir l unit de Dynaline et ou d autres appareils combustion dans l habitation v rifier le bon fonctionnement Ne pas revenir une chambre o...

Страница 38: ...es M me les personnes veill es peuvent ne pas remarquer l alarme si celui ci est couvert par le bruit d une cha ne hi fi radio climatiseur ou d un autre appareil ou par la circulation automobile Dispo...

Страница 39: ...e s jour La manette de commande est situ dans l angle inf rieur gauche avant de l appareil Pour acc der la manette de commande on doit faire pivoter l avant de la caisse vers l avant voir figure 15 NO...

Страница 40: ...Cette inspection doit inclure un contr le complet du fonctionnement de l appareil ceci incluant tous les composants lectriques et m caniques REMARQUE Si le panneau de fa ade de la caisse a t d pos ava...

Страница 41: ...usieurs instructions relatives la s curit qu il convient d observer au cours de la saison de chauffage pour garantir le fonctionnement en s curit de l appareil 1 Ne jamais faire fonctionner l appareil...

Страница 42: ...ration L appareil devrait tre soumis une inspection avant l utilisation et au moins chaque ann e par un technicien qualifi Il peut tre n cessaire de nettoyer plus fr quemment s il y a une accumulation...

Страница 43: ...BK BL Y BK Y R R R R O BR BK BK COMPRESSOR RELAY Y Y L2 R BK L1 WHITE YELLOW BROWN BLACK RED BLUE ORANGE COLOR R W Y BR BL BK CODE O FLAME CONDENSER BK BL MODULE BOARD O BR 1 2 3 4 BUILT IN T STAT PR...

Страница 44: ...EET 3m HORIZONTALLY C CLEARANCE TO WINDOW OR DOOR THAT MAY BE OPENED a a L CLEARANCE ABOVE PAVED SIDEWALK OR PAVED DRIVEWAY LOCATIED ON PUBLIC PROPERTY 7 FEET 2 13m a D VERTICAL CLEARANCE TO VENTILATE...

Страница 45: ...CTUREL STYLE NATUREL GRILLE EN ALUMINIUM FINITION STOCK 1420 DARK GRILLE DE FINITION BRONZE STOCK 1418 INTRODUCTION Ces grilles d coratives sont con ues pour l utilisation comme option ou grille de re...

Страница 46: ...DYNA12AC et DL3 s rie DYNA16AC on peut ajouter une section additionnelle N est pas recommand d utiliser sur les mod les avec thermostats int gr s Si une section additionnelle est n cessaire on peut u...

Страница 47: ...Les dommages caus s par l utilisation ou la mise en sc ne de l unit dans un environnement corrosif 4 Les dommages caus s par une mauvaise application du produit 5 Les dommages caus s par le d faut d e...

Страница 48: ...essous d environ 45 F 13 C quand l appareil est dans l un des modes ATTENTE CHAUFFAGE ou REFROIDISSEMENT Ce fonctionnement peut tre d sactiv si on le d sire Si une protection contre le gel est d sir e...

Страница 49: ...E APPLIANCE MUST BE REPLACED IT MUST BE REPLACED WITH TYPE 105 C WIRE OR TYPE 150 C WIRE WHERE SPECIFIED OR ITS EQUIVALENT 105 C THERMOPLATIC 14 A W G WIRE TGS 200 C 18GA STRANDED TEFLON COATED ROCKER...

Страница 50: ...WHITE BLACK 2 4 3 1 BL BL W W BK IGNITOR RELAY BK ROCKER SWITCH BK BL R R O O 24VAC GND CONT GAS VALVE POWER SUPPLY BOARD CO DETECTOR BL Y BK GY R BL T T NC C T C A NO BR BL BL Y Y BR O 4 3 2 1 BL O...

Страница 51: ...uche SYSTEM pour passer de HEAT COOL V rifiez les num ros de d faut associ s au mode COOL Le menu SERVICE expirera automatiquement et reviendra au r glage pr c dent REMARQUE 1 Pour supprimer les d fau...

Страница 52: ...n du verrouillage 15 Perte de verrouillage du pressostat Contact pressostat ouvert pendant le chauffage Apr s 5 d clenchements du pressostat un verrouillage de 20 minutes commence le code 15 est enreg...

Отзывы: