13-9
CONTROL SYSTEM
SM DLF 1-A.1 GB
13.1.16.2 Indoor Coil Defrost Protection — DLF
ICT
Trend
Fast Increasing Increasing
No Change
Decreasing
Fast Decreasing
< -2
SC
SC
SC
SC
SC
[-2, 0)
D1
D1
D2
D2
D2
[0, 2)
SR
SR
D1
D2
D2
[2, 4)
SR
SR
SR
D1
D2
[4, 6)
Norm
Norm
SR
SR
D1
[6, 8]
Norm
Norm
Norm
SR
SR
> 8
Norm
13.1.16.3 Indoor Coil Overheating Protection
ICT
ICT Trend
Fast Decreasing
Decreasing
No Change
Increasing
Fast Increasing
>62
SC
SC
SC
SC
SC
[60, 62)
D1
D1
D2
D2
D2
[55, 60)
SR
SR
D1
D2
D2
[52, 55)
SR
SR
SR
D1
D2
[48, 52)
Norm
Norm
SR
SR
D1
[45, 48)
Norm
Norm
Norm
SR
SR
I<45
Norm
13.1.17
Compressor Overheating Protection
13.1.17.1 Compressor Overheating Protection for DCI25/35/50/60/72Z
Compressor temperature can be in one of 5 control zones (4 in protection, and 1 normal),
according to the following chart.
Normal
P1
P2
P3
Stop-Compressor
94
98
102
105
CTT
Control Status
Compressor Temperature Increases Else
P1
Normal
Stop Rise
P2
HzDown 1
Stop Rise
P3
HzDown 2
HzDown 1
Stop Compressor
Stop Compressor
Содержание Multi Split DUO 50 DCI
Страница 14: ...4 2 OUTLINE DIMENSIONS SM DLF 1 A 1 GB 4 2 Outdoor Unit DCI 25 35 50 4 3 Outdoor Unit DCI 60...
Страница 15: ...4 3 OUTLINE DIMENSIONS SM DLF 1 A 1 GB 4 4 Outdoor Unit DCI 72Z...
Страница 47: ...7 4 SOUND LEVEL CHARACTERISTICS SM DLF 1 A 1 GB DCI 50 Cooling DCI 50 Heating DCI 60 Cooling DCI 60 Heating...
Страница 48: ...7 5 SOUND LEVEL CHARACTERISTICS SM DLF 1 A 1 GB DCI 72Z Cooling DCI 72Z Heating...
Страница 93: ...15 5 EXPLODED VIEWS AND SPARE PARTS LISTS SM DLF 1 A 1 GB 15 5 Indoor Unit DLF 60 72 DCI E F G D E D D E D...
Страница 96: ...15 8 EXPLODED VIEWS AND SPARE PARTS LISTS SM DLF 1 A 1 GB 15 8 Outdoor Unit DCI 50...
Страница 98: ...15 10 EXPLODED VIEWS AND SPARE PARTS LISTS SM DLF 1 A 1 GB 15 10 Outdoor Unit DCI 60...
Страница 100: ...15 12 EXPLODED VIEWS AND SPARE PARTS LISTS SM DLF 1 A 1 GB 15 12 Outdoor Unit DCI 72Z...