16-39
APPENDIX A
SM DLF 1-A.1 GB
INDOOR UNIT
UNIT LOCATION
UNIT DIMENSIONS
While selecting a place for the indoor unit:
a. Allow max. air flow to the desired space.
b. Allow max return air flow.
c. Ensure adequate drainage of condensed
water.
d. Ensure noise reduction near bedrooms.
e. Leave a minimum 200 mm free space in
the rear side of the unit.
f. Allow a free service access to electrical
box.
h. Allow easy access to the base of the
indoor unit while providing enough space
from the ceiling.
i. Use serrated rubber under the unit and
flexible joints to avoid resonance
vibrations
.
UNIT DIMENSIONS
NOMINAL
CAPACITY
A B C
2.5-5kW
750 696 790
6-7.2kW 1050
996
1090
CLEARENS AROUND THE UNIT AND SERVICE ACCESS