13-18
CONTROL SYSTEM
SM DLF 1-A.1 GB
OUD Diagnostic Table
AO - Alarm output
No
Problem
AO
5
4
3
2
1
1
OCT is disconnected
Yes
0
0
0
0
1
2
OCT is shorted
Yes
0
0
0
1
0
3
CTT is disconnected
Yes
0
0
0
1
1
4
CTT is shorted
Yes
0
0
1
0
0
5
HST is disconnected (when enabled)
Yes
0
0
1
0
1
6
HST is shorted (when enabled)
Yes
0
0
1
1
0
7
OAT is disconnected (when enabled)
Yes
0
0
1
1
1
8
OAT is shorted (when enabled)
Yes
0
1
0
0
0
9
TSUC is disconnected (when enabled)
Yes
0
1
0
0
1
10
TSUC is shorted (when enabled)
Yes
0
1
0
1
0
11
IPM Fault
Yes
0
1
0
1
1
12
Bad EEPROM
No
0
1
1
0
0
13
DC under voltage
Yes
0
1
1
0
1
14
DC over voltage
Yes
0
1
1
1
0
15
AC under voltage
Yes
0
1
1
1
1
16
Mismatch IDU & ODU models
(*SW 35V14 and above)
Yes
1
0
0
0
0
17
No Communication
Yes
1
0
0
0
1
18
Reserved No
1
0
0
1
0
20
Heat sink Over Heating
No
1
0
1
0
0
21
Deicing
No
1
0
1
0
1
22
Compressor Over Heating
No
1
0
1
1
0
23
Compressor Over Current
No
1
0
1
1
1
24
No OFAN Feedback
No
1
1
0
0
0
25
OFAN locked
Yes
1
1
0
0
1
26
Compressor Lock
Yes
1
1
0
1
0
27
Bad Communication
No
1
1
0
1
1
28
Missing ODU configuration
(*SW 35V14 and above)
Yes
1
1
1
0
0
29
Undefined ODU Model
(*SW 35V14 and above)
Yes
1
1
1
0
1
30
For future use
No
1
1
1
1
0
31
Operation condition is exceeded
(*SW 35V14 and above)
Yes
1
1
1
1
1
*
Alarm Output - is on SW 35V14 and above. There is no alarm on SW 35V12 and below/
●
Unit ON Output
The ‘On/Off status’ dry contact will be on (closed), when the indoor mode is not STBY.
If the indoor mode is STBY mode, the ‘On/Off status’ will be off (open).
●
PD/PS(
Presence Detector/Power Shedding)
Function
Contact=open
Contact=short
J9=open
Presence Detector Connection
Last Mode
Force to STBY
J9=short
Power Shedding Function
No limit
Limit NLOAD
Содержание Multi Split DUO 50 DCI
Страница 14: ...4 2 OUTLINE DIMENSIONS SM DLF 1 A 1 GB 4 2 Outdoor Unit DCI 25 35 50 4 3 Outdoor Unit DCI 60...
Страница 15: ...4 3 OUTLINE DIMENSIONS SM DLF 1 A 1 GB 4 4 Outdoor Unit DCI 72Z...
Страница 47: ...7 4 SOUND LEVEL CHARACTERISTICS SM DLF 1 A 1 GB DCI 50 Cooling DCI 50 Heating DCI 60 Cooling DCI 60 Heating...
Страница 48: ...7 5 SOUND LEVEL CHARACTERISTICS SM DLF 1 A 1 GB DCI 72Z Cooling DCI 72Z Heating...
Страница 93: ...15 5 EXPLODED VIEWS AND SPARE PARTS LISTS SM DLF 1 A 1 GB 15 5 Indoor Unit DLF 60 72 DCI E F G D E D D E D...
Страница 96: ...15 8 EXPLODED VIEWS AND SPARE PARTS LISTS SM DLF 1 A 1 GB 15 8 Outdoor Unit DCI 50...
Страница 98: ...15 10 EXPLODED VIEWS AND SPARE PARTS LISTS SM DLF 1 A 1 GB 15 10 Outdoor Unit DCI 60...
Страница 100: ...15 12 EXPLODED VIEWS AND SPARE PARTS LISTS SM DLF 1 A 1 GB 15 12 Outdoor Unit DCI 72Z...