13-3
CONTROL SYSTEM
SM DLF 1-A.1 GB
Target frequency limits as a function of outdoor air temperature (OAT):
OAT Range
Cooling Mode limits
Heating Mode limits
OAT < 6
MaxFreqAsOATC
No limit
6 ≤ OAT < 15
MaxFreqAsOAT1H
15≤
OAT<28
MaxFreqAsOAT2H
28≤ OAT
No limit
13.1.4
Frequency Changes Control
When the unit is running normally , the compressor frequency change rate is 1 Hz/sec.
13.1.5
Compressor Starting Control
13.1.5.1
Compressor starting control for DCI25/35/50/60
Time
Step1
Step2
Step3
Min 10 Minutes
1
Minute
1
Minute
13.1.5.2
Compressor starting control for DCI72Z
Step 1
Whenever the compressor starts up, after it has been off for more than 45 minutes, the compressor
frequency cannot go below
Step1RPS
for 3 continuous minutes (
this rule comes to ensure oil return
to the compressor
).
Step 2
The compressor speed cannot go above
Step2RPS
once after each compressor start up for 3
continuous minutes (
this rule comes to prevent oil exit from the compressor after its start up)
.
Step 3
The speed cannot go higher than
Step3RPS
unless it was operating for more than 1 continuous
minutes between
Step3RPS
– 5 and
Step3RPS
.
After passing above
Step3RPS
, this rule is re-applied when passing below
Step3RPS
-5.
Содержание Multi Split DUO 50 DCI
Страница 14: ...4 2 OUTLINE DIMENSIONS SM DLF 1 A 1 GB 4 2 Outdoor Unit DCI 25 35 50 4 3 Outdoor Unit DCI 60...
Страница 15: ...4 3 OUTLINE DIMENSIONS SM DLF 1 A 1 GB 4 4 Outdoor Unit DCI 72Z...
Страница 47: ...7 4 SOUND LEVEL CHARACTERISTICS SM DLF 1 A 1 GB DCI 50 Cooling DCI 50 Heating DCI 60 Cooling DCI 60 Heating...
Страница 48: ...7 5 SOUND LEVEL CHARACTERISTICS SM DLF 1 A 1 GB DCI 72Z Cooling DCI 72Z Heating...
Страница 93: ...15 5 EXPLODED VIEWS AND SPARE PARTS LISTS SM DLF 1 A 1 GB 15 5 Indoor Unit DLF 60 72 DCI E F G D E D D E D...
Страница 96: ...15 8 EXPLODED VIEWS AND SPARE PARTS LISTS SM DLF 1 A 1 GB 15 8 Outdoor Unit DCI 50...
Страница 98: ...15 10 EXPLODED VIEWS AND SPARE PARTS LISTS SM DLF 1 A 1 GB 15 10 Outdoor Unit DCI 60...
Страница 100: ...15 12 EXPLODED VIEWS AND SPARE PARTS LISTS SM DLF 1 A 1 GB 15 12 Outdoor Unit DCI 72Z...