12-1
F
CONTROL SYSTEM
SM DL
F
1
-A.1 GB
12.4.4.4 Temperature
Compensation
[ @}<!@ ! '<%
@@@ ! % @
on room thermistor.
The temperature compensation can be enabled/disabled by closing/opening J2 on the indoor unit controller.
No compensation will be activated in Forced operation modes.
12.4.4.5 Indoor Fan Control in Heat Mode
% ! !%
@%'[ ! !!
12.4.5
Automatic Cooling or Heating
12.4.5.1 Automatic Cooling or Heating - General
Mode: AUTO
Temp: Selected desired temperature
Fan: Any
Timer: Any
I-FEEL: ON or OFF
12.4.5.2 Control
Functions
a. Switching-temperature between Cooling and Heating is SPT ± 3
O
C.
b. When the AUTO Mode is started with SPT +/-0
O
&% [Q
[&"' % "[
with IFAN operating at low speed. The proper Auto Heat mode or Auto Cool will be
started whenever the RT reaches SPT-1
O
C or SPT+1
O
C respectively.
c. Mode change between Auto Heat & Auto Cool Modes is possible only after the
COMP has been OFF during the last T minutes.
Mode Change
Time, T
Auto Cool to Auto Heat
3 min
Auto Heat to Auto Cool
4 min
!@&`"[%
operate in (Auto) Cool Mode until the conditions for switching from Auto Cool to
[Q
!@Q[%
operate in (Auto) Heat Mode until the conditions for switching from Auto Heat to
[&
Содержание DLF 18 DCI
Страница 11: ...4 2 OUTLINE DIMENSIONS SM DLF 1 A 1 GB 4 2 Outdoor Unit YBDE 018 024...
Страница 31: ...12 3 CONTROL SYSTEM SM DLF 1 A 1 GB 12 2 2 Controller overview 12 2 2 1 Main Controller Indoor Unit DLF 18 24...
Страница 65: ...12 37 CONTROL SYSTEM SM DL A 1 GB 12 9 5 Remote Control RC 8 Reset Operation...
Страница 69: ...12 41 CONTROL SYSTEM SM DLF 1 A 1 GB 12 11 7 Segment Legend 7 7 segments lege end...
Страница 91: ...14 2 SM DLF 1 A 1 GB EXPLODED VIEWS AND SPARE PARTS LISTS 14 2 Indoor Unit DLF 18 DCI...
Страница 95: ...14 6 SM DLF 1 A 1 GB EXPLODED VIEWS AND SPARE PARTS LISTS 14 4 Indoor Unit DLF 24 DCI E F G D E D D E D...
Страница 96: ...14 7 EXPLODED VIEWS AND SPARE PARTS LISTS SM DLF 1 A 1 GB 14 5 Indoor Unit DLF 24 DCI...