The following combinations show the allowed and not allowed capacity group:
ODU Model
Is it allowed capacity group?
Indoor Capacity
0
1
2
3
4
AB (GCD36 DCI)
No
No
No
No
Yes
AV(YBD036-H13/4HP 3Phase)
No
No
No
No
Yes
AE (4HP DCI 3-Phase)
No
No
No
No
Yes
AF (YBD042-H13/5HP DCI 3-Phase)
No
No
No
No
Yes
AG (YBD060-H13/6HP DCI 3-Phase)
No
No
No
No
Yes
AO (YBD042/5HP DCI)
No
No
No
No
Yes
AP (YBD060/6HP DCI)
No
No
No
No
Yes
AS (YBDE018 DCI)
No
No
No
Yes
No
AT (YBDE024 DCI)
No
No
No
No
Yes
AU (YBDE030 DCI)
No
No
No
No
Yes
Capacity group
Capacity Code
Non Connected unit
0
0
1.0
1
1.5
2
1.7
3
2
4
3
12.3.4 Temperature
Measurements
12.3.4.1 Thermistors default value.
Thermistor
Default value
System Reaction
COOL
HEAT
OCT
1°C
1°C
(1)
OAT
43°C
6°C
CTT
43°C
43°C
HST
75°C
75°C
OMT
43°C
43°C
Replaced by OCT
(1)
RGT
43°C
43°C
RLT
43°C
43°C
ICT
43°C
43°C
RAT
SPT+4°C
SPT-4°C
Notes:
(1)
Whenever both OCT and OMT are faulty the compressor will be forced to OFF.
(2)
Thermistor is defined as faulty (shorted/disconnected) if it’s faulty for more than 10 seconds continuously.
During this time, the system uses the last valid temperature
12.3.4.2 The following thermistor faults are detected by the system:
Thermistor
Thermistor is Disconnected
Thermistor is Shorted
OCT
Temp < -35 °C
Temp > 75 °C
OAT
Temp < -30 °C
Temp > 75 °C
CTT
Temp < -30 °C
Temp > 130 °C
HST
Temp < -30 °C
Temp > 125 °C
OMT
Temp < -30 °C
Temp > 75 °C
RGT
Temp < -30 °C
Temp > 75 °C
RLT
Temp < -30 °C
Temp > 75 °C
ICT
Temp < -30 °C
Temp > 75 °C
RAT
Temp < -30 °C
Temp > 75 °C
CONTROL SYSTEM
Содержание DLF 18 DCI
Страница 11: ...4 2 OUTLINE DIMENSIONS SM DLF 1 A 1 GB 4 2 Outdoor Unit YBDE 018 024...
Страница 31: ...12 3 CONTROL SYSTEM SM DLF 1 A 1 GB 12 2 2 Controller overview 12 2 2 1 Main Controller Indoor Unit DLF 18 24...
Страница 65: ...12 37 CONTROL SYSTEM SM DL A 1 GB 12 9 5 Remote Control RC 8 Reset Operation...
Страница 69: ...12 41 CONTROL SYSTEM SM DLF 1 A 1 GB 12 11 7 Segment Legend 7 7 segments lege end...
Страница 91: ...14 2 SM DLF 1 A 1 GB EXPLODED VIEWS AND SPARE PARTS LISTS 14 2 Indoor Unit DLF 18 DCI...
Страница 95: ...14 6 SM DLF 1 A 1 GB EXPLODED VIEWS AND SPARE PARTS LISTS 14 4 Indoor Unit DLF 24 DCI E F G D E D D E D...
Страница 96: ...14 7 EXPLODED VIEWS AND SPARE PARTS LISTS SM DLF 1 A 1 GB 14 5 Indoor Unit DLF 24 DCI...