13-1
4
TROUBLESHOOTING
SM DL
F
1
-A.1 GB
13.5.5
Checking PFC Chock coil
1) Check PFC chock connections – repair if needed.
2) Visually check to see any burn marks on the wires – replace the chock(s) if needed.
3) Disconnect the chock from the driver and check if the 2 ending wires of each chock are shorted
(continuity check) – if they are NOT shorted replace the chock(s), if they are shorted – check the
driver (
13.5.4
).
Replacing PFC chock - (
14.1.17
)
13.5.6
Checking DC Capacitors
1) Check visually for burn marks on the capacitor PCB and the capacitors for swelling casing –
replace if needed.
2) When power is ON - Check that red led is ON, if not check voltage b and - poles to be
according table:
Unit
Voltage
GC036-43 / INV40-50
380±50VDC
YAD036-42-60-H13 / INV40T/50T/60T
560
±5
0VDC
YBD042-60-H11
310
±5
0VDC
3) When power is OFF - Check capacitance b and – poles, should be according table :
Unit
Capacitance
GC036-43 / INV40-50
2820±560μF
YAD036-42-60-H13 / INV40T/50T/60T
1360
±27
0μF
YBD042-60-H11
3360
±67
0μF
Replacing driver -
(14.1.18)
13.5.7
Checking fuse on Main Board
If the 3.15A fuse on the main Board is burnt check the outdoor fans or any other peripheral that can
cause a short:
1) In case of a problematic peripheral - replace it.
2) In case no problematic peripheral replace the burnt fuse.
3) In case of frequent burning fuse, replace the controller.
Replacing main board - (
14.1.13
)
13.5.8
Checking Outdoor Fan Motor
13.5.8.1. YBD018-027
Check motor capacitor.
Check voltage to motor, should be 230-130VAC. If voltage is not in range, replace the motor.
Check that OMT sensor reading is OK.
If motor is Ok, replace the controller.
Содержание DLF 18 DCI
Страница 11: ...4 2 OUTLINE DIMENSIONS SM DLF 1 A 1 GB 4 2 Outdoor Unit YBDE 018 024...
Страница 31: ...12 3 CONTROL SYSTEM SM DLF 1 A 1 GB 12 2 2 Controller overview 12 2 2 1 Main Controller Indoor Unit DLF 18 24...
Страница 65: ...12 37 CONTROL SYSTEM SM DL A 1 GB 12 9 5 Remote Control RC 8 Reset Operation...
Страница 69: ...12 41 CONTROL SYSTEM SM DLF 1 A 1 GB 12 11 7 Segment Legend 7 7 segments lege end...
Страница 91: ...14 2 SM DLF 1 A 1 GB EXPLODED VIEWS AND SPARE PARTS LISTS 14 2 Indoor Unit DLF 18 DCI...
Страница 95: ...14 6 SM DLF 1 A 1 GB EXPLODED VIEWS AND SPARE PARTS LISTS 14 4 Indoor Unit DLF 24 DCI E F G D E D D E D...
Страница 96: ...14 7 EXPLODED VIEWS AND SPARE PARTS LISTS SM DLF 1 A 1 GB 14 5 Indoor Unit DLF 24 DCI...