13-
19
TROUBLESHOOTING
SM DL
F
1
-A.1 GB
13.5.16.2 YBD 018-030
1) Check voltage on the interconnection wiring – should be 22VDC±1VDC. If not:
2) Disconnect the wire cable from the connector on the IDU main board side and Check voltage
on the IDU terminals “N” and “C” – should be 43VDC±1VDC. If not, replace IDU controller. If it is
43VDC:
3) Connect back the wires to the IDU side and disconnect at ODU side. Check voltage on the
interconnection wiring – should be 43VDC±1VDC. If not, replace wiring. If it is 43VDC replace
Outdoor unit controller.