12-23
CONTROL SYSTEM
SM CKDDCI 2-A.3 GB
12.5.11.1 1 Level Logic
P2
P3
Level
Don’t care
1
Normal
Don’t care
0
Overflow
12.5.12 High/Low Pressure Protection
Whenever high or low pressure accrues in the system which extend beind the system pre-defined
limits, the high and low pressure switches turns on (short) and stops the compressor until these
limits are redrawn.
Fault code error 28 (HPS) or 29 (LPS) will be shown until compressor will resume operation.
High Pressure Protection is switching the compressor off immediately
Low Pressure Protection switching OFF the compressor gradually and can take few minutes.
12.6
Technician Test Mode
This test is aimed for the technicians to check the system under a preset compressor and outdoor
fan values while the expansion valves will function according to the normal running mode.
12.6.1
Entering technician mode
o This mode is entered through the outdoor unit using the HMI (refer to user interface
section).
o It can be selected either for cool or heat.
o Technician test is not possible to enter during deicer.
Exiting technician mode
Technician mode will be terminated either when:
o Escaping by the HMI (exit from the ttC or ttH menus)
o 60 minutes are passed from entering
ANY
0
ON
NLOAD
PUMP
OFF
ON
OPER
LED
OFF
Overflow
Water Level
Normal
BLINK
NLOAD is
forced to 0
8 min
8 min
Overflow when
unit is ON
Overflow when
unit is OFF
8 min
Содержание CKD 036
Страница 11: ...4 2 OUTLINE DIMENSIONS SM CKDDCI 2 A 3 GB 4 2 Outdoor Unit GCD 036 DCR 4 3 Outdoor Unit GC 43 DCI...
Страница 26: ...8 1 WIRING DIAGRAMS SM CKDDCI 2 A 3 GB 8 WIRING DIAGRAMS 8 1 Indoor Unit CKD 036 CKD 045 DCI 202052390039...
Страница 35: ...OPTIONAL ACCESSORIES 11 4 SM CKDDCI 2 A 3 GB...
Страница 117: ...15 7 EXPLODED VIEWS AND SPARE PARTS LISTS SM CKDDCI 2 A 3 GB 15 4 3 Outdoor Unit Electronics Assembly...