12-14
CONTROL SYSTEM
SM CKDDCI 2-A.3 GB
12.4.6 Dry
Mode
12.4.6.1 DRY - General
a. Mode
Definition
Mode: DRY
Temp: Selected desired temperature
Fan:
LOW (automatically selected by software)
Timer: Any
I-FEEL: ON or OFF
12.4.6.2 Control
function
a. COMP
Operation
In general – the operation is set by the NLOAD calculation in indoor unit
side.
Other rules are according to section
12.5.2
b. OFAN
Operation
In normal operation OFAN operates together with the COMP.
Other rules are according to section
12.5.4
c.
EEV
Operation
Some as is cool mode (see section
12.5.3)
d. IFAN
Operation
LOW only.
e. RV
RV is in OFF state during DRY mode.
f. HEATERS
HEATERS are in OFF state during DRY mode.
g. Pump
Pump operates according section
12.4.9