12-20
CONTROL SYSTEM
SM CKDDCI 2-A.3 GB
12.5.3.6 EEV opening determination in normal run mode
The target EEV value is the sum of open loop value (OL) and a result of the accumulative
correction values (CV). The EEV corrections are calculated every
EEVCVTConst
seconds.
12.5.4
Outdoor Fan Speed Control
12.5.4.1 Speed
Definition
The outdoor fans can work in 16 speed states controlled by OMT sensor in cool mode and ICT
sensor in heat mode in ralation to outdoor conditions.
12.5.4.2 General
Rules
The fans will be off when the compressor is off unless HST>55 or faulty and than
OFAN_up will remain ON.
Min time for speed change between speed states is 60 seconds.
The fan speed is also related to protections.
Whenever OFAN fault occurs the compressor will be stopped.
12.5.4.3 Night
mode
During night mode, the OFAN and the compressor will be limited to lower speeds (Cool model
only).
12.5.5
RV State Setting
During heat mode (except during Deicing) RV is ON.
During cool/SB mode RV is OFF.
RV status will be changed only if COMP is OFF for 3 minutes or more.
12.5.6
Base Heater Setting
The base heater will be working only when RV is “ON” according to the following graph:
ON
OFF
OAT
0
2
Base
Heater
When OAT is faulty the base heater will be “ON” continuously in HEAT mode.
12.5.7
Crank case heater Operation
The crank case heater operates only when compressor is off and according to CTT as
following:
¦
CV
OL
EEV
EEV
EEV
OFF
ON
-5
0
CTT
Содержание CKD 036
Страница 11: ...4 2 OUTLINE DIMENSIONS SM CKDDCI 2 A 3 GB 4 2 Outdoor Unit GCD 036 DCR 4 3 Outdoor Unit GC 43 DCI...
Страница 26: ...8 1 WIRING DIAGRAMS SM CKDDCI 2 A 3 GB 8 WIRING DIAGRAMS 8 1 Indoor Unit CKD 036 CKD 045 DCI 202052390039...
Страница 35: ...OPTIONAL ACCESSORIES 11 4 SM CKDDCI 2 A 3 GB...
Страница 117: ...15 7 EXPLODED VIEWS AND SPARE PARTS LISTS SM CKDDCI 2 A 3 GB 15 4 3 Outdoor Unit Electronics Assembly...