12-22
CONTROL SYSTEM
SM CKDDCI 2-A.3 GB
12.5.10 Deicing
12.5.10.1 Deicing Starting Conditions
Deicing operation will start when either one of the following conditions exist:
Case 1: OCT is 8 degree lower then the ambient temp and the minimum time from the last deicer
is passed.
Case 2: OCT is 12 degree lower then the ambient temp and 30 minutes from the last deicer wa
passed.
OCT – Outdoor Coil Temperature
Deicing interval time when compressor is first started in heat mode, is 10 minutes if OCT < -2, and
is 40 minutes in other cases.
Deicing interval time is changed (increased/ decreased in 10 minutes steps) as a function of
deicing time.
In case one of the thermistors is bad the deicer will initiate in predefined intervals
Deicer may accrue also when the unit switch to standby and the OCT is 8 degree lower then
ambient temperature.
12.5.10.2 Deicing Protection Procedure
COMP
RV
OFAN
EEV
ON
HEAT
COOL
ON
OFF
EEVDeicerOpen
Any
T1
T2
T3
T3
T1
12
0
Threshold
max. 12 minutes
DT
OCT
T1 = T2 = 36 seconds, T3 = 6 seconds
12.5.11
Condensate Water over Flow Protection
Each of the pins P1, P2, P3 can have two options:
1 – When it is shorted with P4
0 – When it is not shorted to P4
P1
P2
P3
P4
Содержание CKD 036
Страница 11: ...4 2 OUTLINE DIMENSIONS SM CKDDCI 2 A 3 GB 4 2 Outdoor Unit GCD 036 DCR 4 3 Outdoor Unit GC 43 DCI...
Страница 26: ...8 1 WIRING DIAGRAMS SM CKDDCI 2 A 3 GB 8 WIRING DIAGRAMS 8 1 Indoor Unit CKD 036 CKD 045 DCI 202052390039...
Страница 35: ...OPTIONAL ACCESSORIES 11 4 SM CKDDCI 2 A 3 GB...
Страница 117: ...15 7 EXPLODED VIEWS AND SPARE PARTS LISTS SM CKDDCI 2 A 3 GB 15 4 3 Outdoor Unit Electronics Assembly...