12-7
CONTROL SYSTEM
SM CKDDCI 2-A.3 GB
12.4
Indoor Unit Control
12.4.1 Load
calculation
LOAD is calculated according to the difference between actual room temperature and user
set point temperature by PI control.
In high/ medium/ low indoor fan user setting, unit will operate fan in selected speed.
In AutoFan user setting, fan speed will be adjusted automatically according to the calculated
LOAD.
12.4.2
Indoor Fan Control
12.4.2.1 Indoor fan control - FAN Mode
When T/H/M/L speed is set by user, IFAN will work in constant requested speed.
When Auto-Fan is set by user, IFAN speed will be set according to the following graph:
VLOW
Turbo
HIGH
MEDIUM
LOW
DT
3
2
1
0
-1
4
12.4.2.2 Indoor fan control - Cool Mode
When T/H/M/L speed is set by user, IFAN will work in constant requested speed.
When Auto-Fan speed is set by user, IFAN speed will be set according to LOAD(n) as in the
following graph:
IFVLOW
IFLOW
IFMED
IFHIGH
IFTURBO
25
LOAD(n)
IFAN Speed
100
75
50