12-24
CONTROL SYSTEM
SM CKDDCI 2-A.3 GB
12.6.2
Technician mode procedure
Indoor unit will enter technician test at high indoor fan speed.
The outdoor unit will be working normally (according to the run mode control logic) except the
following changes:
o
The dry contacts inputs will be ignored.
o
Protections will be operative for stop compressor only.
o
The compressor and the outdoor fan will be working in target preset values according to the
following table:
Technician Test
Unit
Compressor Speed
OFAN
speed
Cool
Heat
4HP
54
64
800
5HP
71
75
800
6HP
55
63
800
Note:
the values here are for reference only. Each model have its own values.
12.7 User
Interface
12.7.1
User interface description
o
The user interface uses four 7-segments, and 4 keys.
o
The 4 keys are:
-
Scroll - used to scroll between options (up and down)
-
Select - use to select an option
-
Escape - Will go up one level in the menu
o
The user interface concept is Tree menus.
Up
Down
Esc
Select