Error
code
Fault description
Explanation
Action(s)
130
Flue gas temperature limit
exceeded
Heat engine is overheating
Check causes of high temps
Check connection and sensor. Replace
as required
Check connection and chimney.
132
Gas pressure switch safety
shut down
Lack of gas
Check gas supply and pressure
Check connection and component
133
Safety time for establish-
ment of flame exceeded
Lack of gas,
Polarity of mains connection,
safety period,
Reset, if the fault re-occurs more than 3
times, contact AIC technical support.
Check ignition electrode and ionization
current
146
Configuration error sensor/
controlling elements
Check sensor configuration or replace
component
151
LMS14… error, internally
Check parameters (see adjustment table
installer and/or call-up values)
Reset controller and/or replace as re-
quired,
Contact AIC technical support.
152
Parameterization error
Incorrect / Conflicting parame-
ters input.
Verify parameters or reset to default pa-
rameters
153
Unit manually locked
Reset button stuck in
Check reset button
160
Fan speed threshold not
reached
Fan possibly defective, speed
threshold set wrongly.
Check parameters, connections and
component. Replace as required
162
Air pressure switch error
Air pressure switch does not
close
Check connection and adjustments on
air pressure switch. Replace as required.
164
Flow/pressure switch, heat-
ing circuit error
Check connection and switches in HC.
Replase as required
166
Air pressure switch error
Air pressure switch does not
open
Check connection and adjustments on
air pressure switch. Replace as required.
170
Error water pressure sen-
sor, primary side
Check connection and sensor. Replace
as required.
171
Alarm contact 1 active
Correct the active fault
172
Alarm contact 2 active
173
Alarm contact 3 active
174
Alarm contact 4 active
176
Water pressure 2 too high
Release the water to a suitable pressure.
177
Water pressure 2 too low
Top up the system with water to reach a
suitable pressure.
178
Temperature limiter heating
circuit 1
Allow the circuit to cool down and carry
out reset; if the fault occurs several times
inform AIC technical support.
179
Temperature limiter heating
circuit 2
Allow the circuit to cool down and carry
out reset; if the fault occurs several times
inform AIC technical support.
183
Unit in parametrization
mode
Wait until parametrization process is
complete