![AIC N 280 FS Скачать руководство пользователя страница 42](http://html1.mh-extra.com/html/aic/n-280-fs/n-280-fs_installation-and-maintenance-manual_2870757042.webp)
I-42
B-070343_EN • B
P
roduct
I
nstallatIon
Adjustment of Fan Speeds
Conditions:
Adjustment Procedure (Fig. 23)
1. Press the On/Off switch located on the right
side of the boiler.
If starting the boiler for the first time after
installation, the controller will open the
commissioning screen automatically.
2. Perform the commissioning setting of the boil-
er (refer to
“Start-up and Combustion Ad-
justments” on page I-53)
.
3. Control the gas pressure and consumption at
appliance start up.
4. Press the ESC (
3
) button.
5. Press the OK (
2
) button.
6. Press the Info (
1
) button for more than 3 sec-
onds. The access levels are displayed.
7. Rotating the selection knob (
4
), go to:
î
“
Engineer
”. Press OK (
2
) to confirm.
î
“
Burner Control
”. Press OK (
2
) to confirm.
î
“
Required speed ignition
” (Program num-
ber
9512
).
8. Press OK (
2
) to modify the value. The value
starts flashing (
5
).
i
9. Rotating the knob (
4
), adjust the ignition fan
speed for the gas type and boiler type accord-
ing to the table below.
10. Press OK
(
2
) to confirm and save the value.
11. Rotating the knob, go to “
Required speed
LF
” (Program number
9524
).
12. Press OK (
2
) to modify the value. The value
starts flashing (
5
).
13. Rotating the knob (
4
), adjust the minimum fan
speed for the gas type and boiler type according
to the table shown at the bottom of the page.
14. Press OK (
2
) to confirm and save the value.
15. Rotating the knob (
4
), go to “
Required speed
HF
” (Program number
9529
).
16. Press OK (
2
) to modify the value. The value
starts flashing (
5
).
17. Rotating the knob (
4
), adjust the nominal fan
speed for the gas type and boiler type accord-
ing to the table below.
18. Press OK (
2
) to confirm and save the value.
19. Press ESC (
3
) to exit the settings.
Follow-on Task(s)
î
Perform the combustion adjustment. See
“Combustion Adjustment for Gas Conver-
sion” on page I-43.
Fan Speeds
N 280 FS
N 420 FS
N 570 FS
N 840 FS
Gas Type
Ign.
Min
Max.
Ign.
Min
Max.
Ign.
Min
Max.
Ign.
Min
Max.
G20
rpm
1700
880
5530
1700
730
4350
1300
780
4150
1700
800
5630
G25
rpm
1700
1250
5530
1700
730
4350
1300
880
4150
1700
800
5630
G31 (30/37 mbar)
rpm
1700
1500
5070
1700
1210
4290
1200
1100
3910
1700
1470
5360
G31 (50 mbar)
rpm
1500
1500
5070
1550
1210
4290
1100
1100
3910
1600
1470
5360
Fig. 23. Fan Speed Adjustment - Typical Screen
0 4 8 12 16 20 24
OK
ESC
1
3
2
4
5
Burner Control
Required speed LF