![AIC N 280 FS Скачать руководство пользователя страница 27](http://html1.mh-extra.com/html/aic/n-280-fs/n-280-fs_installation-and-maintenance-manual_2870757027.webp)
I-27
B-070343_EN • B
P
roduct
I
nstallatIon
Safety Instructions for the Installation
î
The appliance must be in-
stalled in a dry and protect-
ed area, with an ambient
temperature comprised be-
tween 0 and 45°C.
î
Make sure to protect the appliance and
the heating system against freezing.
î
The appliance must be installed to en-
sure easy access at all times.
î
Use an appropriate means of handling,
suitable to the appliance size and weight.
î
Floor-standing appliances must be in-
stalled on a level base and wall-hung
appliances, on a vertically plumb sup-
port. Material used for base and sup-
port must have suffi cient strength to
support the appliance weight, water
included.
î
Make sure that the appliance is installed
with a suffi cient height to allow the con-
densates to fl ow to the sewer, and/or
allow the installation of a condensate
neutralisation system (as required).
î
When lifting, moving or installing the
appliance, be careful not to drop it.
Once in position, make sure that the
appliance is secured.
î
Install all pipes and ducts without stress
to prevent any leaks from occurring.
î
When the appliance is con-
nected to the electrical net-
work, it must be earthed.
î
Make sure that a fuse or circuit breaker
of the recommended rating is installed
outside the appliance, so as to be able
to shut the power down.
î
Do not touch the appliance with any
wet body parts when it is supplied with
electrical power.
î
Before performing any operation on
the electrical circuit, isolate the electri-
cal supply of the appliance through the
external power-cutting device (fuse,
circuit breaker, etc.)
î
All connections (electrical, fl ue pipe,
hydraulic, gas) must be carried out
in accordance with current standards
and regulations in force.
î
If the appliance is installed against a wall
made of heat-sensitive material, such as
wood, a suitable insulation must be pro-
vided by the installer between the appli-
ance and the wall surface.
î
Comply with the clearance dimensions
provided in this manual, to prevent any
hot part of the appliance from being
too close to the walls or any combus-
tible material.
î
Make sure to maintain a safe distance
of 200 mm from fl ammable materials;
the boiler room may not be used as a
storage location for material.
î
Do not store any fl ammable, corrosive or
explosive products next to the appliance.
î
Do not install the appliance in a loca-
tion where chemical vapours or dust are
present in the ambient or combustion air.
î
If the appliance is used on professional
premises such as hairdresser’s, cleaning
company, painter’s, etc. where chloride
products, solvents, paints, dust, etc. are
likely to contaminate the air, make sure
to install the appliance in a dedicated
boiler room so that the appliance is sup-
plied with clean combustion air.
î
Install a condensate neutralisation
system according to the applicable lo-
cal regulations and standards.
î
If the boiler is intended to be used
with G31 liquefi ed petroleum gas
(propane), installing the boiler below
ground level can be hazardous and
prohibited in some countries. Please
refer to applicable local regulations
for installation requirements.