Chapter 3
47
Configuration
Configuration Methods
10 At the Telnet prompt (
>
), enter the configuration values you want to
change or set. (You only need to specify the non-default values that
you want.) The following information will help you set the values
correctly.
The following table lists the configuration values you can set using
Telnet. The following information shows the syntax you should use
and provides tips to help you to change or set the configuration
values correctly.
NOTE
By using the Telnet configuration method, the LAN hardware address
(
hardware-addr:
) value is automatically set to the correct hardware
address for this LAN/GPIB Gateway. Do not change the hardware
address value via Telnet. Its value in the Telnet configuration table is for
information purposes only.
Configuration Value
Telnet Command
Default Value
Hostname
hostname:
E2050
IP Address
ip:
192.0.0.192
Default Subnet Gateway Address
gateway:
0.0.0.0
Subnet Mask
subnet-mask:
0.0.0.0
Syslog Server Address
syslog-svr:
0.0.0.0
BOOTP
bootp:
ON
LAN Timeout
lan-timeout:
0
I/O Timeout
io-timeout:
120
IP Allow List
allow:
* (All allowed)
GPIB Address
hpib-address:
21
GPIB Interface Name
hpib-name:
hpib
1
GPIB Logical Unit
hpib-unit:
7
1
Change name to
gpib0
for VXI-11 compatibility
Содержание E2050
Страница 1: ...Agilent E2050 LAN GPIB Gateway Installation and Configuration Guide ...
Страница 2: ......
Страница 10: ...10 ...
Страница 11: ...11 1 Introduction ...
Страница 23: ...23 2 Installation ...
Страница 32: ...32 Chapter 2 Installation Installing the Hardware Notes ...
Страница 33: ...33 3 Configuration ...
Страница 63: ...63 4 Administration ...
Страница 80: ...80 Chapter 4 Administration Configuring the Gateway Notes ...
Страница 81: ...81 5 Troubleshooting ...
Страница 99: ...99 A Specifications ...
Страница 102: ...102 Specifications Specifications Notes ...
Страница 103: ...103 Glossary ...
Страница 111: ...Part Number E2050 90003 Printed in U S A E0701 E2050 90003 ...