AM Series Boilers and Water Heaters
CHAPTER 9 – OPERATION
OMM-0100_0D
AERCO International, Inc.
•
100 Oritani Dr.
•
Blauvelt, NY 10913
Page
105
of
154
GF-146
Ph.: 800-526-0288
03/28/16
Factory Menu
BOILER
PARAMETERS
WATER HEATER
PARAMETERS
PARA#
PARAMETER
DESCRIPTION
RANGE
FACTORY
SETTINGS
BURNER
1
BURNER
2 TO 4
BURNER
1
BURNER
2 TO 4
3016
Reset curve design:
Minimum heating supply
temperature
68°F to 194°F
68°F
68°F
68°F
N/A
N/A
3017
Maximum supply
temperature (This
parameter overrules
3015 parameter)
68°F to 194°F
179°F
179°F
179°F
179°F
179°F
3018
Minimum supply
68°F to 194°F
89°F
89°F
89°F
89°F
89°F
3020
Type of water
flow
sensor
0 = N/A
1 = DN8
2 = DN 10
3 = DN 15
4 = DN 20
5 = DN 25
3
4
4
4
4
3022
Minimum water
pressure
0 to 74 PSI
14
14
14
14
14
3035
Minimum water
flow
0 to 26.4 GPM
3.9
3.9
3.9
3.9
3.9
3050
Number of slave
burners
0 to 3
3
399 = 1
500 = 1
750 = 2
1000 = 3
3
399 = 1
500 = 1
750 = 2
1000 = 3
3
3085
Modbus Address
0 - 126
0
0
0
0
0
3086
Number of Modbus Stop
Bits
1 or 2
2
2
2
2
2
3100
Venting Type
PVC, CPVC,
PP, or SST
PVC
PVC
PVC
PVC
PVC
3101
N/A
N/A
N/A
N/A
N/A
Switch
“S4”
Position of Switch “S4”
On or Off
On
On
Off
On
Off