9.16 Installer Menu
This menu of parameters is available to
qualified technicians for the purpose of analyzing the
function of, and making adjustments to, the unit.
Parameters for “Burner 1” are applicable for that burner only. If you want to see the same
parameters for the other burners you must connect the display to the burner you want to see per
the illustration in Figure 8-3.
To enter and make changes in the Installer Menu, perform the following steps:
Installer Menu Navigation and Adjustment
1. To enter the Installer Menu, press and simultaneously hold down both the
RESET
and
buttons or 5 seconds until the icon is displayed.
, then release the buttons.
After entering the Installer Menu, the 2000 series of parameters, as shown in the menu table
below, are available for display and editing.
2. To scroll through the list of parameters, press buttons
and
.
3. Once the desired parameter is displayed, it can be selected for editing by pressing the
RESET
button once (the displayed value will start blinking) and then using the
and
buttons to change the value, up or down.
4. To confirm the new value, press and release the
RESET
button before moving to the next
parameter.
5. To exit the Installer Menu, press and hold RESET button for more than 5 seconds until the
icon is no longer shown in the display.
Installer Menu
PAR#
DESCRIPTION
UM
RANGE
BOILER
FAC.SET
W.H.
FAC.SET
USER
2001
Burner 1 minimum Power
%
1 to 50
1
1
2002
Burner 1 maximum Power
%
1 to 100
100
100
2003
CH mode
nn
00: Constant setpoint w/ enable/disable
01: Outdoor reset w/ enable/disable
02: Outdoor reset (ignores enable/disable)
03: Constant setpoint (ignores
enable/disable)
04: Remote setpoint (0-10V control)
0
0
2004
Burner 1 Wait time after max differential
sec
10 to 30
30
30
2005
Local post pump time (and of the Burner 1
Motorized valve)
sec
10 to 900
240
240
2010
System test: Burner 1 (Master)
\
Off, Low, Ign, High (Set parameter to
OFF to exit from this state)
OFF
OFF
2011
System test: Local pump (and of the Burner 1
Motorized valve)
\
On or OFF
OFF
OFF
2012
System test: CH pump
\
On or OFF
OFF
OFF
2013
System test: DHW pump
\
On or OFF
OFF
OFF