AM Series Boilers and Water Heaters
CHAPTER 10 – MAINTENANCE
OMM-0100_0D
AERCO International, Inc.
•
100 Oritani Dr.
•
Blauvelt, NY 10913
Page
129
of
154
GF-146
Ph.: 800-526-0288
03/28/16
Condensate System Inspection and Maintenance
- Continued
8. Replace the condensate cover and reinsert the condensate collection tank assembly back
into the unit.
WARNING!
The condensate collection tank
must be filled with water to
prevent flue gas emissions from escaping during unit operation.
Failure to comply with this requirement can result in dangerous
levels of carbon monoxide.
9. Open the manual gas shutoff valve.
10. Restore electrical power to the unit and return to service.
WARNING!
The condensate neutralizer tank MUST be installed correctly into
the unit, as shown in Figure 4-8. If you do not install the
condensate collection tank into its correct position, it will result in
combustion gases will entering the room and creating a
dangerous condition.