AM Series Boilers and Water Heaters
CHAPTER 10 – MAINTENANCE
Page
124
of
154
AERCO International, Inc.
•
100 Oritani Dr.
•
Blauvelt, NY 10913
OMM-0100_0D
03/28/16
Ph.: 800-526-0288
GF-146
Replacing the BURNER Thermal Insulation
- Continued
6. Install the wool gasket in the back of the new burner thermal insulation (see Figure I).
7. Install the new burner thermal insulation on the burner (see Figure J).
Figure I: Wool Gasket w/ Thermal Insulation Figure J: Install Thermal Insulation
8. Assembly the ignition and detection electrodes, paying attention to the correct position of the
red gasket (shown with arrows in Figure K).
9. Screw the electrodes in place (see Figure L).
Figure K: Reassemble the Electrodes Figure L: Tighten the Electrodes
10. Before reinstalling the burner, clean the surface on which the gasket will sit (shown with
arrows in Figure M) to ensure a good seal.
11. Install the reassembled fan burner assembly (see Figure N) in the heat exchanger by
performing the steps in section 10.15 –
Removing the Burner
in reverse order.
Figure M: Clean Gasket Surface Figure N: Burner Reassembly
12. Repeat the instructions above on the remaining burners in the unit.