AM Series Boilers and Water Heaters
CHAPTER 9 – OPERATION
Page
100
of
154
AERCO International, Inc.
•
100 Oritani Dr.
•
Blauvelt, NY 10913
OMM-0100_0D
03/28/16
Ph.: 800-526-0288
GF-146
9.15 User Menu
Press and hold the RESET button for 5 seconds to invoke the User Menu. When entering the
User Menu, the 1000 series of parameters, shown in the chart below, are available for display, but
cannot be edited.
Parameters for “Burner 1” are applicable for that burner only. If you want to see the same
parameters for the other burners you must connect the display to the burner you want to see per
the illustration in Figure 8-3. Parameters labeled “MULTIBURNER” apply to the entire unit.To
navigate the Installer Menu, perform the following:
User Menu Navigation
Press the buttons
and
to scroll through each of the parameters. All parameters
in the User Menu may be displayed, but cannot be edited.
User Menu
PAR#
PARAMETER'S DESCRIPTION
UNITS
1001
Burner 1 supply temperature
°F
1002
Indirect water heater temperature
°F
1004
Outdoor sensor temperature (Boilers Only)
°F
1006
Burner 1 Flue gas temperature
°F
1007
Burner 1 Return temperature
°F
1008
Burner 1 Ionisation current
µA
1009
State of the General pump (and of the Burner 1 check valve)
ON/OFF
1010
State of the CH pump (Boilers Only)
ON/OFF
1011
State of the DHW pump
ON/OFF
1012
Calculated CH setpoint (when outdoor sensor s activated) (only for 199 and 250 mode)
°F
1040
Burner 1 Actual Fan speed
rpm/min
1041
Burner 1 Ignition fan speed
rpm/min
1042
Burner 1 Low power fan speed
rpm/min
1043
Burner 1 High power fan speed
rpm/min
1051
Burner 1 Last lockout number
\
1052
Burner 1 Last Blocking error
\
1053
Burner 1 Number of flame failures
#
1055
Burner 1 Number of failed ignitions
#
1056
Burner 1 Total hours of operation tor boiler
Hr x 10
1057
Burner 1 Total hours of operation for DHW
Hr x 10
1059
*Burner 1 Interval between Lockouts.
May be: 1MIN; 2:HRS; 3:0AY; 4:WK
For parameters 1059 and 1060, the first digit displays the unit used, and
the second digit displays the number of those units. For example 1:34
would mean 34 minutes. A display of 4:3 would indicate 3 weeks.
1060
*Burner 1 Interval between Blocking errors.
May be: 1:MIN; 2:HRS; 3:DAY; 4:WK
1062
Burner 1 Heating Water flow
GPM
1101
MULTIBURNER: Number of burners ON
n
1102
MULTIBURNER: System temperature ·
°F
1103
MULTIBURNER: My Burner Into Lockout
/
1104
MULTIBURNER: Any Sumer into Stocking Error
/
1106
MULTIBURNER: System is in emergency mode
/
1107
MULTIBURNER: Current multi-burner setpoint
°F
1120
MULTIBURNER: Burner 1 fire rate
%
1121
MULTIBURNER: Burner 2 fire rate
%
1122
MULTIBURNER: Burner 3 fire rate
%
1123
MULTIBURNER: Burner 4 fire rate
%
*Examples of displayed timer values and equivalent time lengths:
1:29 = 29 minutes 3:15 = 15 days
2:12 = 12 hours 4:26 = 26 weeks