76
60T - 280T
COSMOGAS
17 - USE
2024
Climate control: delivery temperature corresponding to
spring outdoor temperature
°C
From 0 to 40
40
N/A
2027
Night-time reduction
°C
From 0 to 50
10
N/A
2040
N/A
N/A
N/A
N/A
N/A
2041
N/A
N/A
N/A
N/A
N/A
2042
Burner 1 - Protection against frequent ignitions: time
secs
From 10 to 900
180
180
2043
Burner 1 - Protection against frequent ignitions: tempera-
ture differential
°C
From 0 to 20
16
5
2062
Post circulation domestic hot water pump
secs
From 10 to 255
240
240
2063
Maximum time priority DHW
min
From 1 to 60
30
N/A
/
2067
Priority production of DHW
/
0 = Priority lasts the time set at
parameter 2063;
1 = OFF, the domestic hot water
does not have priority over central
heating;
2 = ON, the domestic hot water
always has priority over central
heating;
2
N/A
2100
Energy saving display
min
From 0 to 30 = delay in switching off
in minutes.
5
5
2101
Multi-burner: emergency mode
/
Yes or No
Yes
Yes
2102
Multi-burner: Emergency temperature adjustment
°C
from 20 to 65
45
45
2103
Multi-burner: ignition delay
secs
from 1 to 900
15
15
2104
Multi-burner: switch-off delay
secs
from 1 to 900
15
15
2105
Multi-burner: delta temp. burner ignition
°C
from 0 to 20
5
5
2106
Multi-burner: delta temp. burner switch-off
°C
from 0 to 20
5
5
2107
Multi-burner: maximum increase in temp. compared to
that calculated
°C
from 0 to 20
10
4
2108
Multi-burner: maximum reduction in temp. compared to
that calculated
°C
from 0 to 20
20
4
2109
Multi-burner: Next burner ignition
%
from 1 to 100
70
70
2110
Multi-burner: Next burner switch-off
%
from 1 to 100
10
10
2111
Multi-burner: Burner rotation
gg
from 0 to 9
6
6
2113
Multi-burner: Modulation start-up delay
min
from 0 to 60
5
0
2114
Burner 1: Primary circuit pump switch-off time
secs
from 0 to 255
240
240
2200
Forcing: All Burners together.
\
Off, Low, Ign, High
OFF
OFF
2201
Forcing: Burner 1 (Master).
\
Off, Low, Ign, High
OFF
OFF
2202
Forcing: Burner 2.
\
Off, Low, Ign, High
OFF
OFF
2203
Forcing: Burner 3.
\
Off, Low, Ign, High
OFF
OFF
2204
Forcing: Burner 4.
\
Off, Low, Ign, High
OFF
OFF
N/A = Not Applicable
17.16 - Diagnostics
During normal operation of the boiler, viewer “N” in figure 17-1
continuously shows the boiler’s work status, by means of the
following indications:
Parameter
Description of parameter
Display on screen “N” in Figure 17-1
AFro
Anti-frost function on
Boiler temperature (°C)
DHW with puffer operation status
Temperature of DHW (°C)
Operation status of central heating or instant DHW
Output temperature (°C)