10.4 - MYDENS boiler
INAIL safety devices
The boiler is supplied as standard
without
the INAIL safety
devices.
WARNING! All boilers of more than 35 kW of power
must, at the installer’s responsibility, be equipped with
safety devices as provided for by Compilation “R” issued
by the INAIL.
WARNING! Isolation devices must not be installed
between the boiler and the safety valve (detail “7” in figure
10-3 and “15” in figure 10-4).
To make installation convenient, COSMOGAS supplies,
on
request
, INAIL kits complete with required devices and the
segment designed to house them.
In figure 10-3 the kit for models 70T and 140T.
Figure 10-3 Key
1 = Nipple
2 = Gasket
3 = Manifold
4 = Catch basin for sensor Valve “11”
5 = INAIL thermometer
6 = INAIL pressure gauge
7 = INAIL safety valve
8 = Connection group
11 = INAIL fuel isolation valve
12 = Inspection basin
13 = INAIL safety thermostat
14 = INAIL safety pressure switch
15 = INAIL safety pressure switch
16 = Expansion tank connection joint
WARNING! The sensor of valve “11” (figure 10-
3) is positioned in the basin for sensor “4” and closed
with the relative anti-unthreading locking screw.
In figure 10-4 the kit for models 210T and 280T
Figure 10-4 Key
1 = Fixing nuts and bolts
2 = Gasket
3 = INAIL safety pressure switch
4 = INAIL safety pressure switch
5 = Connection group
6 = INAIL safety thermostat
7 = Manifold
10 = INAIL fuel isolation valve
11 = Catch basin for sensor Valve “10”
12 = Inspection basin
13 = Expansion tank connection joint
14 = INAIL pressure gauge
15 = INAIL safety valve
16 = INAIL thermometer
WARNING! The sensor of valve “10” (figure 10-
4) is positioned in the basin for sensor “11” and closed
with the relative anti-unthreading locking screw.
10 - INSTALLATION - Plumbing connections - MYDENS boiler