14 - INSTALLATION - Flue gas outlet and air intake pipe
14.1.2 - Split system
The boiler is supplied as standard with the joint to connect
the flue gas outlet. For installation proceed as shown in
figure 14-2.
1.- insert pipe “E” into reducer “C” taking care that the
gasket provided is in the correct position;
Polypropylene pipes, more resistant to the formation of
condensate, must be installed.
Take particular care with the installation of pipes in the
part that goes through the wall to the outside. Normal
maintenance operations must always be possible;
therefore, install the pipes in a sheath so that they can be
slid out.
The horizontal sections must always have a slope of at
least 2% towards condensate outlet devices.
The boiler is already provided with a condensate
collector that must be connected to an outlet pipe (see
section 12).
WARNING! This condensate outlet is designed
to drain away all of the liquid produced by a single
appliance. If more than one boiler is installed, each
boiler should be provided with its own condensate
outlet.
The flue gas exhaust/air intake system can be extended up
to a maximum distance as indicated in section 19. Each 90°
bend has a loss equivalent to that reported in section 19.
WARNING! The flue gas outlet terminal must be
correctly protected against the effects of the wind.
WARNING! Mechanically secure the joints
between the various component elements of the
exhaust and intake pipe, through the use of fixing
systems or equivalent systems. See figure 14-4.
WARNING! The temperature of the exhaust
pipe can reach 90°C during operation. If the pipe
passes through walls that are sensitive to these
temperatures, insert a protective heat-insulating
sheath.
WARNING! The outlet duct must be suitably
supported by rigid rods positioned not more than 1 m
from each other. The rods must be fastened to rigid
walls that can take the weight of the duct itself.
Figure 14-4 – Fixing the exhaust and intake pipes
Figure 14-2 – Installing the
split system
Figure 14-3 - Assembled system
C
E
F
020014.01.028
Air Inlet
Flue
gas outlet
020014.01.029
Air Inlet
Flue
gas outlet
Содержание AGUADENS 210T
Страница 93: ...93 60T 280T COSMOGAS 18 MAINTENANCE Figure 18 15 Multi wire wiring diagram part 2 continued from previous page...
Страница 96: ...96 60T 280T COSMOGAS 18 MAINTENANCE Figure 18 16 Multi wire wiring diagram part 3 continued from previous page...
Страница 117: ......
Страница 118: ......
Страница 119: ......