![Adveco AGUADENS 210T Скачать руководство пользователя страница 103](http://html1.mh-extra.com/html/adveco/aguadens-210t/aguadens-210t_instructions-for-installation-use-and-maintenance-manual_2858811103.webp)
103
60T - 280T
COSMOGAS
AGUADENS TECHNICAL DATA
UM
70T
140T
210T
280T
Type (Type of flue gas exhaust/air intake)
B23 ; B23P
B23 ; B23P
Category
II2H3P
II2H3P
II2H3P
II2H3P
EU type approval certificate (PIN)
0476CR1272
0476CR1272
0476CR1272
0476CR1272
Max. heat input “Qn” PCI (PCS)
kW
69.9 (77.6)
140.0 (155.4)
210.0 (233.1)
280.0 (310.8)
Min. heat input “Qm” PCI (PCS)
kW
14.7 (16.3)
14.7 (16.3)
14.7 (16.3)
14.7 (16.3)
Max. useful output power (50/30) “Pn”
kW
73.5
147.1
220.7
294.3
Efficiency at max. useful output power (50/30) PCI (PCS)
%
105.1 (94.7)
105.1 (94.7)
105.1 (94.7)
105.1 (94.7)
Min. useful output power (50/30) “Pm”
kW
15.6
15.6
15.6
15.6
Efficiency at min. useful output power (50/30) PCI (PCS)
%
106.3 (95.8)
106.3 (95.8)
106.3 (95.8)
106.3 (95.8)
Gas flow rate
G20
m
3
/h
7.39
14.80
22.20
29.61
G25
m
3
/h
8.60
17.22
25.83
34.43
G30
kg/h
5.51
11.03
16.55
22.06
G31
kg/h
5.43
10.87
16.30
21.73
Gas supply pressure
G20
mbar
20
20
20
20
G25
mbar
25
25
25
25
G30
mbar
30
30
30
30
G31
mbar
37
37
37
37
Gas supply minimum pressure
G20
mbar
17
17
17
17
G25
mbar
20
20
20
20
G30
mbar
25
25
25
25
G31
mbar
25
25
25
25
Gas supply maximum pressure
G20
mbar
25
25
25
25
G25
mbar
30
30
30
30
G30
mbar
35
35
35
35
G31
mbar
45
45
45
45
Primary heat exchanger water content
l
5.7
11.4
17.1
32.8
Minimum operating water flow rate with motorised valves
l/h
/
2700
2700
2700
Minimum operating water flow rate without motorised valves
l/h
2700
5400
10800
10800
Instant DHW production (dt 30°C)
l/min
35.3
70.7
106.0
141.4
Instant DHW adjustment range
°C
20 - 80
20 - 80
20 - 80
20 - 80
Maximum temperature for safety intervention
°C
95
95
95
95
Maximum pressure “PMS”
bar
11
11
11
11
Minimum pressure
bar
1
1
1
1
Rated power supply voltage
V
230
230
230
230
Rated power supply frequency
Hz
50
50
50
50
Absorbed electrical power
W
150
300
430
590
Electrical protection rating
IP20
IP20
IP20
IP20