60T - 280T
COSMOGAS
16.4 - Conversion of boiler models 70T
from one type of gas to another
WARNING! Read these instructions carefully
before making the gas change:
- The installation, calibration or modification of the gas
boiler must be carried out by specialised people, in
compliance with the law;
- Check and be certain that the type of gas which
is powering the appliance is compatible with the
adjustment kit in your possession;
- Do not supply the boiler with a type of gas other than
those anticipated.
Figure 16-4 – Replacing the gas nozzle
Figure 16-3 - Raising gas valve
Figure 16-2 – Removing the gas valve
A
H
M
020010.01.020
L C
B
020010.01.021
G
020010.01.019
Contents:
The kit (supplied as standard with the boiler) is made up of
- label certifying the new type of gas, a gas nozzle for each
burner and an instruction sheet;
To carry out the change of gas, proceed as follows:
1 - Turn off the boiler by moving the main switch to OFF (detail
“T” in figure 17-1);
2 - Turn off the gas supply cock;
3. - Open the boiler casing as shown in section 18.2;
4 - Undo junction “H” in figure 16-2;
5 - With the aid of a screwdriver, remove fork “A” in figure 16-2;
6 - Remove the gas valve with junction “C” as in figure 16-3
(paying attention to the OR “L” in figure 16-3);
7 - Replace nozzle “G” in figure 16-4 with the one in the kit,
checking it corresponds in diameter to that shown in table 16-8;
8 - Replace the gas valve paying attention to the correct
position of the OR “L” in figure 16-3 and to the joint gasket
“H” in figure 16-2;
9 - Replace fork “A” in the locking housing;
10 - Tighten joint “H” in figure 16-2;
11 - Open the gas supply valve;
12 - Check that there are no leaks from joint “H” in figure 16-2;
WARNING!
Test the gas seal using a soap
and water solution only. The use of naked flames
is prohibited.
13 - Turn on the boiler by moving the main switch to ON (detail
“T” in figure 17-1);
14 - Completely undo screw “E” in figure 16-6 in an
anticlockwise direction;
15 - Check gas pressure by following section 16.7, the minimum
pressure must not be less than 10 mbar while the maximum
must not exceed 45 mbar;
16 - Check and adjust the CO2 following the procedure in
section 16.8 and checking the value in figure 16-8;
WARNING!
The measurements taken must be
done with guaranteed calibrated instruments that
ensure an accurate reading.
17.- Check the boiler’s power by following section 16.9;
18.- apply the adhesive data plate
(see figure 16-7) to the right-
hand side of the boiler, in place of the label that identified the
old setting status, to certify the boiler’s new setting status,
as follows: apply label “B” if the boiler has been converted
from methane to LPG; apply label “A” if the boiler has been
converted from LPG to methane.
WARNING!
If you smell gas:
A - Do not turn on any electrical device, including a
telephone, or any item that could cause sparks;
B - Immediately open doors and windows to create
a draught that can quickly clear the gas from the
room;
C - From another room, or from a neighbour’s
property, immediately call a professionally
qualified technician or the gas supply company.
Call the Fire Service if the former are not available.
16 - START-UP
020022.01.008
NO
YES