![Adveco AGUADENS 210T Скачать руководство пользователя страница 24](http://html1.mh-extra.com/html/adveco/aguadens-210t/aguadens-210t_instructions-for-installation-use-and-maintenance-manual_2858811024.webp)
24
60T - 280T
COSMOGAS
C
B
A
020010.01.011
D
020010.01.012
Figure 5-1 - Undoing transport pallet screws
5.1 - Selection of place of installation
WARNING! Do not store any inflammable
material in the boiler’s immediate vicinity.
WARNING! Do not install the boiler on carpet.
WARNING! The boiler must be installed in a
room in which there is a supply of air for ventilation
and combustion, regardless of whether it is taken
from outside (sealed combustion) or from inside
(combustion in ventilated room).
WARNING! Inadequate ventilation of the boiler
can cause elevated air temperatures.
WARNING! Make sure that the intake and
outlet openings are the right size and that there are no
obstructions and blockages. If the problem cannot be
resolved, do not start up the boiler. Please keep in mind
these restrictions and the risks they may cause to the
operator.
WARNING! Liquified Petroleum Gas (LPG) - The
installation needs particular attention: LPG boilers
must not be installed in trenches, cellars or similar
rooms in which the gas, which is heavier than air, could
hang. LPG powered boilers must not be installed in
places below floor level or basements. If these remarks
are not respected, explosions could result and cause
serious injury to people, death or enormous material
damage.
5 - INSTALLATION - Place of installation
WARNING! If installed in rooms with a thin floor,
a resonating noise could be generated. The installation
of noise-reduction elements is required.
WARNING! Do not let too much dust accumulate
on the boiler.
WARNING! The boiler must only be installed on
a solid floor, which takes its weight and is level.
Before installing the appliance, the central heating system
and, if necessary, the domestic hot water system must be
washed thoroughly in order to remove any residues or
impurities which could compromise the working order of
the boiler.
This boiler is not designed to be installed in the open
air, it must not be exposed to temperatures below 0.5°C
or above 50°C. Choose a place inside the building or
somewhere sheltered from weather such as rain, wind,
sun and, above all, frost.
This appliance must be installed in a place where
water leakages from the appliance itself, from the joints
between the pipes or from any drainage from the safety
valve, cannot cause damage to materials or items below
it.
Choose the room and suitable position for installation,
taking into account the following factors:
- connection to smoke outlet/air intake ducts;
- connection to gas adduction duct;
- connection of the water supply;
- connection to the central heating system;
- connection to domestic hot water system (where present);
- electric connection;
- connection to outlet for condensate produced by the
boiler;
- electric connection of the room thermostat;
- connection to safety valve outlet;
- connection to the outdoor temperature sensor (where
applicable);
- room ventilation.