Figure 12-3 - Correct installation of condensate outlet pipe
Figure 12-1 - Condensate neutraliser
C
A
D
B
E
C
A
D
B
E
020010.01.029
Figure 12-2 - Condensate outlet
12.1 - Condensate outlet
The boiler has inside it a siphon system and condensate
neutraliser to evacuate condensates (see figures 3-3, 3-5 and
3-7, details “2” and “3”) and prevent combustion products from
escaping, the end of which meets duct “5” in figures 3-3, 3-5
and 3-7. This end must be funnelled into another anti-odour
siphon (responsibility of the installer) so as to prevent bad
smells from coming back into the room.
In particular, the condensate outlet system must:
be performed with a pipe with an internal diameter equal
to or greater than 13 mm;
be installed in such a way as to prevent the liquid from
freezing; therefore pay attention to any external sections.
It is prohibited to drain into gutters or rainwater drainpipes;
slope continuously towards the drain point; avoid high
points, which could pressurise the pipe;
Figure 12-2 shows how a condensate disposal system must
be created downstream from the boiler.
12 - INSTALLATION - Disposal of condensate
YES
NO
Figure 12-2 Key
A = Condensate outlet duct start stopper;
B = Condensate inlet;
C = Stoppers for duct inspection;
D = Anti-odour siphon system;
E = Atmospheric connection (duct vent);
F = Condensate outlet;
G = Condensate outlet pipe;