1.3
Page 23
MPC-
143. User’s Manual
8
"Limits verification" tab
This tab enables users to set up limits verification raising events for issuing alerts when
condition is met. To create the list, follow the next steps:
1.
Choose “Count of limits” in order to start creating the number of positions
desired;
2.
Choose “Type of limit” (this must to be done first) among the following options:
o
Over H: event will be generated when the value is above the high limit.
o
Under L: event will be generated when the value is below the low limit.
o
Over H & Under L: event will be generated when the value is out of the
range between high and low limit.
o
Under H & Over L: event will be generated when the value is within the
range between high and low limit.
o
Equal L: event will be generated when the value is equal to the low limit.
3. Enter register number you want to control or choose from Main fields list (To
create and/or edit list of limit’s values use file limits.csv, that is in program’s
folder.);
4. Enter data type, corresponding to data type of used register;
5. Choose limits;
6. Delay time (in seconds), if you want to filter accidental ar short time events;
7. Finally, add a code of event (value must to be from 0 to 99 and will be used for
alerts SMS sending)
Figure 22.
“Limits verification” tab
9
"Alerts" tab
MPC-143 is able to send short SMS text messages based on discrete inputs status or
events generated by limits verification feature. In order to set up the SMS alert
component, follow the next steps:
1.
Select “Enabled” checkbox.
2. Choose how many phone numbers will get SMS messages (max. 5 phone
numbers).
3. Fill table with phone numbers.
NOTE: User can block SMS sending feature during controller testing procedures by
selecting from discrete input list which one
blocks SMS sending (if “none” is selected –
SMS blocking is disabled). Closed discrete input disables SMS sending.
9.1 SMS Alerts on discrete inputs
All
discrete inputs‘ state (ON and OFF) can be used for sending SMS alerts. For each
discrete channel‘s state any text can be added (max. 160 symbols).
Содержание MPC-143