background image

Pub.  42004-358A 

     GAI-TRONICS 3030 KUTZTOWN RD.  READING, PA  19605 USA

610-777-1374  

„

  800-492-1212  

„

  Fax:  610-796-5954 

V

ISIT WWW

.

GAI

-

TRONICS

.

COM FOR PRODUCT LITERATURE AND MANUALS

 

G A I - T R O N I C S ®  

A   H U B

 

B E

 

L

 

L   C

 

O M

 

P

 

A N Y  

Model 10439-102 

Electrical Safety Barrier for Centra-Page 

Systems 

Confidentiality Notice 

This manual is provided solely as an operational, installation, and maintenance guide and contains 
sensitive business and technical information that is confidential and proprietary to GAI-Tronics.  
GAI-Tronics retains all intellectual property and other rights in or to the information contained herein, 
and such information may only be used in connection with the operation of your GAI-Tronics product or 
system.  This manual may not be disclosed in any form, in whole or in part, directly or indirectly, to any 
third party. 

General Information 

The Model 10439-102 Electrical Safety Barrier is used in GAI-Tronics Centra-Page communications 
systems.  This system provides industrial quality intra-plant communications in both hazardous and non-
hazardous areas. 

GAI-Tronics Centra-Page system provides dependable paging and party line communications for rugged 
and hazardous industrial facilities.  Centra-Page features centrally-located electronics that provide 
environmental protection and unitized amplification for easy maintenance.  Standard Centra-Page 
cabinets can support up to 30 handset stations and in most cases up to 60 paging speakers. 

The listed handset stations, when installed with a corresponding Model 10439-102 Electrical Safety 
Barrier in accordance with Control Drawing No. 72979, provides intrinsically safe communications in 
Class I, Div. 1, Group C and D hazardous areas.  One barrier is required for each handset station located 
in a Class I, Div. 1, Group C and D hazardous area in a Centra-Page system. 

In Centra-Page systems, barriers are not installed in conjunction with speakers or horn/driver 
combinations: speakers and horn/driver combinations located in Div. 1 hazardous areas must be 
explosion-proof and be installed with explosion-proof conduit. 

Отзывы: