Pressure Gauges:
Compressor Discharge (Head) Pressure: Compressor discharge and
refrigerant condensing pressure. Pressure operating range will vary depending on
refrigerant type.
Compressor Suction (Low) Pressure: Compressor suction and refrigerant
evaporating pressure. Pressure operating range will vary depending on
refrigerant type.
6.2 COOLANT SYSTEM
A. Reservoir:
Provides coolant storage during non operating periods. An internal baffle
separates ‘from process’ and ‘to process’ fluid flows during operating periods.
B.
Process Pump: Provides fluid to the central system.
C.
Standby Pump: Optional pump to provide backup for the process or evaporator pump.
D.
Evaporator pump: Provides consistent flow through the brazed plate evaporators to
maintain full capacity.
E.
Flow switch: Protects the evaporator from possible freezing caused by too little flow.
F. Freezestat: Protects the system from potential freezing. Factory adjusted to 40°F. For
operating temperatures below 48°F, see section 6.7 on page 39.
G.
Level control switch: Indicates water level in reservoir.