OACS Central Chillers : with MG Series Control Instrument
Page: 84
ADVANTAGE ENGINEERING, INC.
525 East Stop 18 Road Greenwood, Indiana 46142
317-887-0729 Fax: 317-881-1277
Service Department Fax: 317-885-8683
Email: [email protected]
Register Coil Use Range Units Notes
Temperature Setpoint
1
R/W
0-250 F
Temperature Setpoint 2
2
R/W
0-250 F
2nd Setpoint
Temperature High Alarm
3
R/W
0-50
F
Deviation Value
Temperature Low Alarm
4
R/W
0-50
F
Deviation Value
Flow Low Alarm
5
R/W
0-99
GPM
Deviation Value
To Process Temperature
6
R
0-255 F
From Process Temperature
7
R
0-255 F
To Process Flow Rate
8
R
0-99
GPM
Process Status
9
1-16 R
Pump
On
Bit 0
Alarm
Bit 1
Alarm
Process
Bit 2
Alarm
Machine
Bit 3
Hi
Temp
Bit 4
Lo
Temp
Bit 5
Bit 6
Bit 7
Bit 8
Lo
Flow
Bit 9
Bit 10
Bit 11
Bit 12
Bit 13
Bit 14
Bit 15
Machine Status 1
10
17-32 R
Pump
On
Bit 0
Alarm
Bit 1
Alarm
Process
Bit 2
Alarm
Machine
Bit 3
HTL
Switch
Bit 4
Lo
Temp
Bit 5
Bit 6
Lo
Press
Bit 7
Bit 8
Lo
Flow
Bit 9
Bit 10
Bit 11
Pump
O/L
Bit 12
Heater
Fail
Bit 13
Phase
Wrong
Bit 14
Bit 15
Machine Status 2
11
33-48 R
Pump
On
Bit 0
Alarm
Bit 1
Alarm
Process
Bit 2
Alarm
Machine
Bit 3
Sensor
Fail
Bit 4
Bit 5
Valve
Error
Bit 6
Bit 7
Bit 8
Bit 9
Bit 10
Bit 11
Bit 12
Bit 13
Bit 14
Bit 15
Process Status No Alarm*
12
49-64 R
Pump
On
Bit 0
Alarm
Bit 1
Alarm
Process
Bit 2
Alarm
Machine
Bit 3
High**
Temp
Bit 4
Low**
Temp
Bit 5
Bit 6
Bit 7
Bit 8
Lo
Flow
Bit 9
Bit 10
Bit 11
Bit 12
Bit 13
Bit 14
Bit 15
Machine Status 1 No Alarm* 13
65-80 R
Pump
On
Bit 0
Alarm
Bit 1
Alarm
Process
Bit 2
Alarm
Machine
Bit 3
HTL
Switch
Bit 4
Lo
Temp
Bit 5
Bit 6
Bit 7
Bit 8
Lo
Flow
Bit 9
Bit 10
Bit 11
Bit 12
Heater
Fail
Bit 13
Phase
Wrong
Bit 14
Bit 15
Machine Status 2 No Alarm* 14
81-96 R
Pump
On
Bit 0
Alarm
Bit 1
Alarm
Process
Bit 2
Alarm
Machine
Bit 3
Sensor
Fail
Bit 4
Bit 5
Valve
Error
Bit 6
Bit 7
Bit 8
Bit 9
Bit 10
Bit 11
Bit 12
Bit 13
Bit 14
Bit 15
Heartbeat-On Then Off
15
97-112 R
1 Sec
Coil 97
Bit 0
Bit 1
Bit 2
Bit 3
16
Second
Bit 4
Bit 5
Bit 6
Bit 7
Bit 8
Bit 9
Bit 10
Bit 11
Bit 12
Bit 13
Bit 14
Bit 15
Machine Control
16
113-128 R
Machine
On/Off
Bit 0
Alarm
Ack.
Bit 1
Bit 2
Bit 3
Bit 4
Bit 5
Bit 6
Bit 7
Bit 8
Bit 9
Bit 10
Bit 11
Bit 12
Bit 13
Bit 14
Bit 15
Notes:
IP Address 200.0.0.203 (typical)
Subnet Mask 255.255.255.0
Gateway none
Protocol RTU
Address 1
Baud Rate 9600
* These registers are mirrors of 9-11. They are used to indicate errors without sounding an alarm. They can be used to indicate when a problem is present
even when the alarm is shut off.
•• These bits will activate when the temperature is outside of the range set by the setoint and the deviation. This doesn not indicate an error.
8.9
MODBUS REGISTERS