K.
Once all safety provisions are made, the temperature control set point may
now be lowered to the desired operating temperature.
L. WARNING:
do not use any type or brand of automotive antifreeze.
Automotive antifreeze contains corrosion inhibitors - silicates - designed for
compatibility with the materials in automotive engines. Unfortunately, silicates
can gel and cause deposits to foul and insulate heat exchanger surfaces. In
your chilling system that can mean higher energy costs, high pumping costs,
and possibly even shut downs for system cleaning. We recommend the use
of DowFrost or Monsanto DFS-1.