3.2 START UP / OPERATION PROCEDURE
A.
System Fill
1.
For operating temperatures from 48°F to 80°F use water to fill the unit. For
operating temperatures below 48°F a water and propylene glycol mixtures must
be used. An inhibited propylene glycol can be used for operating temperatures
above 48°F if desired to prevent corrosion and scaling. Use the minimum ratio
that is recommended by the glycol manufacturer. See section 8 of this manual for
more information.
2.
The unit has an internal reservoir which must be filled and maintained for proper
operation. The unit has a level switch mounted at the proper water level in the
reservoir.
3.
WATER QUALITY CONTROL. Lack of, as well as, improper water treatment can
damage the chilling unit. The services of competent water treatment specialist
should be obtained and their recommendations followed. It is the equipment
owner’s responsibility to prevent damage from foreign material or inadequate
water treatment. See water treatment section in section 1.6 of this manual for
more information.
4.
FOR AUTOMATIC FILL: Always install a manual shut off valve on the make-up
water supply on the outside of the unit. When electrical power is applied to the
unit but the On/Off Selector is in the ‘off’ position open the owner supplied shut
off valve. The level switch will activate the make-up solenoid which will open
and the water supply will fill the reservoir tank. Do not use automatic fill when
operating at temperature below 48°F or when ambient temperature may be
35°F or lower.
5.
MANUAL FILL: Add fluid directly to the reservoir. When the pump is first started,
as process lines are filled and air is purged, additional fluid may be required to
restore the reservoir to the correct level. Verify reservoir level via the coolant
sight glass.
6.
Do not use deionized water in this unit unless your unit was specifically designed
for use with deionized water. Consult factory if not certain.
Typical Insulated Reservoir
Reservoir Sight Glass