OACS Central Chillers : with MG Series Control Instrument
Page: 46
ADVANTAGE ENGINEERING, INC.
525 East Stop 18 Road Greenwood, Indiana 46142
317-887-0729 Fax: 317-881-1277
Service Department Fax: 317-885-8683
Email: [email protected]
4.1 UNIT WILL NOT START
A.
Power off. Check main disconnect.
B.
Main line open. Check fuses.
C.
Loose terminals. Tighten terminals with POWER OFF.
D.
Control circuit open. Check control voltage fuses and transformer.
4.2 COMPRESSOR HUMS BUT WILL NOT START
A.
Contactor problem. Check contacts and contactor operation.
B.
Low voltage. Check voltage at main and at the unit. If voltage is OK at the main but low
at the unit, increase wire size. If low at main, consult your local power company. Voltage
must be +/- 10% nameplate rating.
C.
No power on one phase of a three phase unit. Check fuses in control panel and main
disconnect. Also check unit wiring, main plant fuse and wiring. If the problem is with the
main power supply coming into the plant, call the local power company.
D.
Loose terminals. Power off and follow all company lock-out tag-out procedure before
tightening terminals.
4.3 SHUTS OFF ON HIGH PRESSURE LIMIT
Note: Units may be equipped with either an adjustable or non-adjustable
“fixed” high pressure switch. If the refrigerant pressure exceeds the
setting of the adjustable switch it must be manually reset when the
discharge pressure falls to a safe level. The non-adjustable “fixed”
high pressure switch will automatically reset when the discharge
pressure falls to a safe level.
A.
Insufficient condenser air flow. Check condenser filter for dirt, fins
may be plugged with dirt or foreign material. Also, check for proper fan
rotation.
Note: All enclosure panels on the air-cooled condenser must be
attached.
B.
Fan motor not operating. Have electrician check fuses and wiring,
motor starter and overloads, and motor. Repair or replace motor if defective.
C.
Improperly set high pressure control. Have refrigeration serviceman reset or replace
the control if defective.
Adjustable High
Pressure Switch
Fixed High
Pressure Switch
WARNING: Before troubleshooting or servicing this unit, follow all company lock-out tag-out
procedures.