5.6 CHECKING THE REFRIGERANT CHARGE
A.
All standard chillers are manufactured with thermostatic
expansion valves as the metering device to the evaporator.
B.
All standard chillers have a refrigerant sight glass with a
moisture indicator. To check the refrigerant charge under
normal operating conditions:
1.
Remove the plastic cap covering the sight glass.
2.
Start the chiller and allow system pressures and
temperatures to stabilize.
3.
With the unit operating at 100% capacity (not in
the “capacity control” mode) the sight glass should
appear clear with no foam or bubbles evident. If
foam or bubbles are evident, the chiller has suffered
from a loss of refrigerant and should be checked by
a qualified refrigeration technician.
4.
The “dot” in the middle of the sight glass is the moisture indicator. It should
appear green at all times. A white or yellow color indicates moisture has invaded
the refrigeration system, which is detrimental to the life of the compressor. The
filter-drier should be replaced by a qualified refrigeration technician.
5.7 PROPER CLEANING PROCEDURE FOR BRAZED PLATE EVAPORATORS
A.
The brazed plate evaporator is made of stamped stainless steel plates, furnace brazed
together with copper based joints. The complex geometry of
the flow passages promotes turbulent flow which gives high
efficiency and reduces fouling by mineral deposits. Large
solids such as plastic pellets or chunks of mineral deposits will
collect at the water inlet port at the evaporator and restrict flow
through some of the passages. If this possibility exists, the
Manufacturer recommends filters or strainers be added to the
“from process” line. If the evaporator becomes fouled there are
a couple of methods for cleaning.
B.
To begin, remove the piping to the “water in” port at the
evaporator. Remove any solids that have collected at this
point. Then back flush the evaporator to remove any solids
that may be trapped between the plates (see back flush
procedure below). If there are mineral deposits adhered to the
plates, the evaporator must be back flushed with a mild acid
solution (5% phosphoric or 5% oxalic acid is recommended.)
After cleaning rinse with clear water before returning to
service. Continue with step C on the next page.
C.
Back flushing procedure:
1.
Turn off all power to the machine. For chillers with a reservoir tank, drain the tank
Refrigerant Sight Glass
Brazed Plate Evaporator