A1-User’s Manual
150
40.16 PID wake frequency
Range: '40.14' ~ 400.0 Hz in 0.01 Hz
Initial value: 0.00 Hz
Program the frequency reference when the VFD wakes up from the sleep mode for the
specified operation
40.17 PID feedback monitor
Range: 0.00 ~ 100.0%
Real time display of PID feedback
40.18 PID output monitor
Range: 0.00 ~ 100.0%
Real time display of PID output
40.19 PID integral reset source
0: Not selected ----- Initial value
1: Selected
2: DI1
3: DI2
4: DI3
5: DI4
6: DI5
7: DI6
8: DI7
9: DI8
Selects the source of the PID integral reset
Set 0: Not selected
Always off
Set 1: selected
Always on
Set 2~9 : DI1~ DI8
It works by digital input which is selected